Data Sheet

BELLS & BUZZERS
© Copyright 2004 Edwards
TECHNICAL INFORMATION
5-7
4" Bell
6" Bell
EASY INSTALLATION USING THE SUPPLIED ADAPTAPLATE
1. Pull wires through
center hole and connect to
binding post.
3. Tighten front screw to complete
installation. (Two screws on 4
inch bells)
2. Slip Adaptabel onto sturdy
hanger and push home.
SIGNAL INPUT LOAD CHARACTERISTICS**
Light Source Operating Max. off state Continuous on Surge (inrush/duration)
Cat. No. Voltage leakage current (mA) Current (mA) Amps/milliseconds
340-4N5 120V AC 60 Hz 25 62 0.095/4
340-6N5 120V AC 60 Hz 25 70 0.15/4
340-10N5 120V AC 60 Hz 25 70 0.15/4
**This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.
dB at DC Coil
Cat No.* Volts Amps VA 1m / 10 ft. Res (Ohms)
340-4E5 12 0.620 7.4 94 / 88 13
340-4FM 16 0.460 7.4 22
340-4G5 24 0.310 7.4 50
340-4N5 120 0.062 7.4 1300
340-4R5 240 0.031 7.4 5000
340-6E5 12 0.700 8.4 98 / 92 8
340-6FM 16 0.500 8.0 13
340-6G5 24 0.350 8.4 30
340-6N5 120 0.070 8.4 700
340-6R5 240 0.035 8.4 2650
340-10G5 24 0.350 8.4 102 / 96 30
340-10N5 120 0.070 8.4 700
340-10R5 240 0.350 8.4 2650
*Gong Size in inches denoted by suffix in catalog number.
2 13/32"
(61 mm)
4 1/2"
(114 mm)
3 11/16"
(94 mm)
7 1/8"
(181 mm)
4 13/16"
(122 mm)
10 1/2"
(267 mm)
10" Bell
D-04