Lectro CPR® Operator’s Manual ® Lectro CPR Operator’s Manual Alpha Technologies, Inc. 3767 Alpha Way Bellingham, WA 98226 Tel: 360-647-2360 Fax: 360-671-4936 Web: www.lectro.
Lectro CPR® Operator’s Manual Table of Contents TABLE OF CONTENTS ........................................................................................................................................ 2 LIST OF TABLES & FIGURES............................................................................................................................. 3 IMPORTANT SAFETY INSTRUCTIONS ..............................................................................................................
Lectro CPR® Operator’s Manual List of tables & figures FIGURE 1.1-1: POLE MOUNT INSTALLATION ........................................................................................................... 7 FIGURE 1.2-1: GROUND MOUNT PROFILE (CONCRETE OR CONCRETE COMPOSITE PAD) ........................................... 9 FIGURE 1.2-2: GROUND MOUNT (FRONT VIEW OF 4 BATTERY CABINET WITH GROUND SKIRT) ................................... 9 FIGURE 1.2-3: POLE MOUNT (FRONT VIEW OF 8 BATTERY CABINET)........
Lectro CPR® Operator’s Manual IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for the Lectro CPR® Uninterruptible Power Supply (UPS). These instructions should be followed during installation and maintenance of the power supply, batteries, cabinet, status monitor and any options and/or ancillary equipment. CAUTION: RISK OF ELECTRIC SHOCK.
Lectro CPR® Operator’s Manual EC DECLARATION OF CONFORMITY Units that are labeled with a CE mark comply with the following EU directives: 73/23/EEC Council Directive on equipment designed for use within certain voltage limits. 93/68/EEC Amending Directive 72/23/EEC. 89/336/EEC Council Directive relating to electromagnetic compatibility. The EC Declaration of conformity is available upon request for products with a CE mark.
Lectro CPR® Operator’s Manual 1: Cabinet Installation 1.1 Pole Mounting NOTE: Pole mounting the cabinet should be done in accordance with the local agreement between the cable operator and the utility company. NOTE: A bucket truck and other suitable equipment, such as spikes and safety harness, should be used during installation or service of pole-mounted cabinets. To mount the Lectro CPR® UPS to a utility pole perform the following steps: 1.1.
Lectro CPR® Operator’s Manual 1.1.8 Refer to Section 1.3 for Electrical Connections. Figure 1.1-1: Pole Mount Installation 1.2 Ground Mounting Although ground mounting the CPR cabinet can be accomplished by several methods, the following procedure is recommended: 1.2.1 1.2.2 Select an appropriate site. Check with other local utilities for buried plant before site location is finalized. Remove the turf and level an area of approximately 4" greater than the foot print of the CPR cabinet.
Lectro CPR® Operator’s Manual 1.2.3 1.2.4 1.2.5 1.2.6 1.2.7 1.2.8 1.2.9 1.2.10 1.2.11 1.2.12 From the disconnect box, install conduit to the power supply site and turn a stub up to extend above grade level. Drive a suitable ground rod according to local codes (refer to Figure 1.2-1). Install appropriate size conduit for the output connections and turn a stub up to extend 1" above the pad surface cast into the concrete.
Lectro CPR® Operator’s Manual Electrical Supply Conduit for Direct wiring installa- M16-2.0 tion. 1” (2.5 cm) Conduit 79 cm 21.6 cm Minimum. 21.6 cm 66 cm 13.7cm 92 cm 63 cm 10 cm Figure 1.2-1: Ground Mount Profile (Concrete or Concrete composite pad) External Indicator Lamps Padlock Hasp Optional Ground Coastal Skirt Locks Figure 1.
Lectro CPR® Operator’s Manual Figure 1.2-3: Pole Mount (Front View of 8 battery cabinet) Optional Location for “Feed- AC Input Thru” Conduit Adaptor Connection Pole Mount- Ground Lug ing Bracket Figure 1.
Lectro CPR® Operator’s Manual Typical Placement of Disconnect Breaker on Rear of Cabinet Coax “Feed Thru” Seizure Adaptor at Rear Clamp of Bottom Shelf “Snap in” Connector (to power supply output) Figure 1.2-5: Coax “Feed Thru” Adapter Normal Location (Bottom Shelf) 1.3 Electrical Connections WARNING: Be sure the utility (mains) disconnect is off and that no conductors are energized before proceeding. To connect wiring, perform the following steps: 1.3.1 Open the cabinet doors. 1.3.
Lectro CPR® Operator’s Manual 1.3.3 1.3.4 1.3.5 1.3.6 1.3.7 1.3.8 Using the receptacle (if provided), connect the AC high input (black) to the copper receptacle terminal, the AC neutral (white)to the silver receptacle terminal, and the utility protective ground (green) to the green receptacle terminal. The screw tighten torque is 20 lb-in. Position all wiring neatly in the receptacle box and install the receptacle and then the receptacle cover. NOTE: Some cabinets do not have receptacles.
Lectro CPR® Operator’s Manual 2 : Power Supply 2.1 Installation Refer to Section 1 for installation of the pole mount or ground mount enclosure. NOTE: The CPR module weighs 56 lbs/25 kg. (65 lbs./30 kg for the 24 amp model), and the center of gravity is offset to the right. The unit may be lifted using both of the lifting handles on the front of the module. CAUTION: When pulling the unit forward from a shelf, be sure to support the right hand rear corner. Figure 2.1-1: CPR Cabinet-Completely Wired 2.1.
Lectro CPR® Operator’s Manual 2.1.3 Connect the green ground wire from the CPR UPS to the back of the mounting bolt that holds the exterior ground clamp to the wall of the enclosure. Use the #10 hardware provided. 2.1.4 For those power supplies with IEC power cords, plug the cord into the receptacle on the left side of the power supply. Use only an HAR-approved power cord for 50 Hz installations. Tighten the screw on the clamp until the power cord is secure. 2.1.
Lectro CPR® Operator’s Manual THE CPR SYSTEM IS NOW READY TO BE ENERGIZED. FOLLOW THE OPERATING PROCEDURE IN SECTION 2.2. 60 Hz Units (15 amp) A AC Output Cable B Output Voltage Select C Battery Power Cable D AC Input Temp. Probe Fig. 2.1-2 Input/Output Voltage, Temp. Probe Connection points 50 Hz Units A AC Output Fitting D (Green and Yellow cable may be used for output A connection) B Output Voltage Select B C Battery Power Cable D AC Input C Temp. Probe Fig. 2.
Lectro CPR® Operator’s Manual D 60 Hz Units (24 amp) A A AC Output Cables (2) B Output Voltage Select C Battery Power Cable B D AC Input C Temp. Probe Fig. 2.1-4 Input/Output Voltage, Temp. Probe Connection points Front Panel (All Units) E Weak Battery LEDs F Battery Breaker G Test Points H LED Display J CPR Communicator Module K Inverter “ON” LED L Output “ON” LED Figure 2.
Lectro CPR® Operator’s Manual BATTERY INPUT TEMPERATURE PROBE RED BLACK Upper Shelf Negative: (Black) Middle: (Orange) Positive: (Red) Lower Shelf TEMP PROBE INPUT Middle: Longer lead (Orange) FRONT OF ENCLOSURE Figure 2.1-6: Battery Sensing and Temperature Probe Connection – Parallel Strings BATTERY INPUT TEMPERATURE PROBE RED Upper Shelf BLACK Negative: (Black) Middle: (Orange) Positive: (Red) TEMP PROBE INPUT Middle: Longer lead (Orange) If not used, tuck connection out of the way.
Lectro CPR® Operator’s Manual 2.2 Operation CPR UPS STARTUP AND INVERTER TEST 2.2.1 Verify that all connections to the CPR have been made correctly as described in Section 2.1. 2.2.2 Verify that the desired output voltage has been selected (48V, 60V, 75V, or 87V) via the connection at the left side of the CPR module. Check to see that the AC input cord and Battery power cables are plugged in. 2.2.
Lectro CPR® Operator’s Manual 2.2.6 Check the front panel test points with a true RMS voltmeter. CABLE AC OUT should read within 3-5% (maximum range is tap dependent) of the configured output voltage (48, 60, 75, or 87 V). BATTERY should read between 45 and 56 Vdc, depending on the age, temperature, and state-of charge of the batteries. 2.2.7 Verify that the external LEDs on the CPR outdoor cabinet are functioning. In normal operation, the green external LED will be ON solid, (not flashing).
Lectro CPR® Operator’s Manual 2.3.2 Open the cabinet. Check tightness of all battery, internal ground, and output connections. Observe condition of batteries. If the cabinet shows signs of excessive dust or moisture, check for lost vent screens. Repair as required, and note any unusual conditions for future reference. 2.3.3 Inspect the input surge suppressor (if installed) for obvious damage. If it appears intact, check its operation with a megger or a similar device to ensure that it is functioning.
Lectro CPR® Operator’s Manual Lectro CPR Power Supply Maintenance Log Sheet For use with the maintenance procedures in the Operator’s Manual.
Lectro CPR® Operator’s Manual 2.4 Troubleshooting Table 2.4-1: Troubleshooting guide Symptom No AC output to coax cable Possible Cause What To Do Utility failure Notify local Power Co.. External input breaker open or tripped Re-close breaker. Verify breaker is HIGH MAGNETIC type. AC power cord loose/unplugged Re-insert plug into receptacle. Utility voltage or frequency (or generator output) is out of range.
Lectro CPR® Operator’s Manual AC Input “High” red LED is lit AC input voltage is above 156 (or 299 for 230V nominal units, or 276 for 240V nominal units, or 286V for 220V nominal units) VAC— unit will be in Standby mode, running on battery AC Input “Low” red LED is lit. AC input voltage is below 96 (or 161 for 230v nominal units, or 192 for 240V nominal units, or 154V for 220V nominal units)VAC—unit will be in Standby mode, running on battery Load “>100%” red LED is lit. CPR unit is loaded >100%.
Lectro CPR® Operator’s Manual 2.5 Specifications Table 2.
Lectro CPR® Operator’s Manual 120V Extd Range 220V International 230V International 230V Euro (CE) 240V (24 A) Nominal Input Voltage Input Voltage Range in % Input Voltage Range 120V [+30%to -20%] 96V to 156V 220V [+30%to -30%] 154V to 286V 230V [+30%to -30%] 161V to 299V 230V [+15%to -20%] 184V to 265V 240V [+15%to -20%] 192V to 276V Nominal Input Current (Rest Mode) Input Frequency 13A 60 Hz, +/- 3Hz 7A 60 Hz, +/- 3Hz 7A 50 Hz, +/- 3Hz 8A 50 Hz, +/- 3Hz 11A 60 Hz, +/- 3Hz Output Regulati
Lectro CPR® Operator’s Manual 3.1 Safety CAUTION: Short circuit danger: Do not rest tools or equipment on top of batteries. Do not allow batteries to become shorted as an explosion may occur causing severe injury. Do not open or mutilate batteries. Released electrolyte is extremely harmful to skin and eyes. Do not dispose of batteries in fire as an explosion may occur. CAUTION: Government regulations may require that batteries be recycled.
Lectro CPR® Operator’s Manual 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6 Connect the red battery cable which comes from the gray connector on the CPR module to the positive (+) terminal of the left battery. Refer to Figure 3.3-1 for details. Torque all connections to 60 inch-pounds (6.8 Newton-meters). Connect the three (3) battery interconnection jumpers as shown in Figure 3.3-1. Torque all connections to 60 inch-pounds (6.8 Newton-meters). Confirm that the CPR DC circuit breaker is off (down).
Lectro CPR® Operator’s Manual 3.4 Additional Battery String Tools required: 10mm Metric socket Inch-pound torque wrench Multimeter NOTE: This procedure assumes that the additional battery string is being installed in a Lectro brand cabinet. 3.4.1 Confirm that the CPR DC circuit breaker is off (down). 3.4.2 Place the batteries in the bottom of the cabinet with the negative terminals (-) at the rear of the cabinet. Refer to Figure 3.4-1 for details 3.4.
Lectro CPR® Operator’s Manual RED BLACK Upper Shelf Lower Shelf FRONT OF CABINET Figure 3.4-1: Battery Connections – Parallel Strings 3.5 Maintenance 3.5.1 WHILE IN STORAGE Always make sure a battery is fully charged before placing it into storage. Never charge batteries in a gas-tight container. Always store batteries in a cool, dry location. Optimum temperature is 25°C (77°F). Always monitor battery, open-circuit voltage at least once every 12 months.
Lectro CPR® Operator’s Manual A different state of charge condition likely exists if the open circuit voltage for any battery in a string deviates from its neighbor by more than ± 0.25 volts. Never leave a battery in a discharged state for any length of time. 3.5.3 PERIODIC MAINTENANCE Never forget to periodically check batteries for proper terminal attachment torque every 12 months.
Lectro CPR® Operator’s Manual 4: Status Monitor 4.1 Installation The communication module installs in the same basic manner for all three levels of status monitoring. The external connections will be different as defined in Section 4.3. 4.1.1 4.1.2 4.1.3 4.1.4 4.1.5 Turn off the CPR Unit, and remove AC Power. Remove the communication module cover plate (if applicable). Locate and pull out the ribbon cable with the connector, inside of the CPR Communicator module slot.
Lectro CPR® Operator’s Manual 4.2 Operation The operation of the status monitor is automatic and carries out its functions without the direct intervention of the operator. The purpose of the status monitor is to indicate the operating conditions of the CPR power supply. There are three levels of status monitoring: LEVEL ONE is used to indicate locally (at the power supply) only (see Figure 4.3-1). This can be a combination of the external cabinet LED indicators and/or the LED’s on the CPR power supply.
Lectro CPR® Operator’s Manual 4.3 Configuration Level One – Refer to Figure 4.3-1 Level Two – Refer to Figure 4.3-2 Level Three – Refer to Figure 4.3-3 Weak Battery LEDs (One for each string) Battery Sensing Harness (connects to battery terminals) Wiring to External Cabinet LEDs Figure 4.
Lectro CPR® Operator’s Manual Weak Battery LEDs (One for each string) RS-232 DB-9 Port for connection to Transponder, Modem, Laptop PC or customer-supplied PDA. Battery Sensing Harness (connects to battery terminals) Wiring to External Cabinet LEDs Door Tamper Switch connector (shown with shorting jumper) Figure 4.
Lectro CPR® Operator’s Manual 4.4 Maintenance 4.4-1 Test the CPR Communicator for the correct signals by monitoring the specific CPR module at the headend. 4.4-2 Simulate the “General Alarm” signal by removing the plug (or shorting jumper) on the front of the CPR module. Verify this alarm is received at the headend. 4.4-3 Check all wiring connections. Refer to Section 2.1. The CPR Communicator Module should be tested and the connections checked on a regular basis.
Lectro CPR® Operator’s Manual 4.5 Troubleshooting Because it is impossible to account for every possible symptom and solution in a CATV Network, the following troubleshooting suggestions should be used as a general guideline. Refer to Figure 4.5-1 Table 4.