M Series Multi-Output Power Supply Chargers Installation Guide Models Include: • AL300ULM • AL400ULM • AL600ULM • AL1012ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. - 6 amp @ 12VDC or 24VDC. - 10 amp @ 12VDC. • AL1024ULM - 10 amp @ 24VDC. For a red enclosure add an “R” suffix to the part #, e.g. AL300ULMR Models AL300ULM, AL400ULM and AL600ULM can be built in a larger enclosure. Add an “X” suffix to the part #, e.g. AL400ULMX Rev.
Overview: These multi-output access control power supply/chargers are specifically designed for use with access control systems and accessories. These units convert a 115VAC, 60Hz input into five (5) individually protected 12VDC or 24VDC outputs (see specifications). Each output will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes.
Supervision: Specifications: Supervision (cont’d): • AC fail supervision (form “C” contact). • Low battery supervision (form “C” contact). • Battery presence supervision (form “C” contact). • Power fail supervision relay (form “C” contact rated 1 amp @ 28VDC). Additional Features: • Power supply is complete with enclosure, cam lock, and battery leads.
AL300ULM Output Output Voltage and Stand-by Specification Charts: Switch Position 4 hr. of Stand-by & 5 Minutes of Alarm Stand-by = 2.5 amp Alarm = 2.5 amp 12VDC/40AH Battery ON 24VDC/12AH Battery OFF ----------------------------------------- 24VDC/40AH Battery OFF Stand-by = 2.5 amp Alarm = 2.5 amp 24 hr. of Stand-by & 60 hr. of Stand-by & 5 Minutes of Alarm 5 Minutes of Alarm Stand-by = 1.0 amp Stand-by = 300mA Alarm = 2.5 amp Alarm = 2.
Fig. 1 - AL300ULM, AL400ULM CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuses with the same type and rating (see marking on the board). Do not expose to rain or moisture. 5A 250V Fire Alarm Interface Power-limited L Fig.
Fig. 2 - AL600ULM CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture. 5A 250V Divider L Fire Alarm Interface Power-limited G Wire Strap (from Enclosure to Door) NEG (-) INPUT POS (+) NC C NO NC C NO DRY OUTPUT POWER FAIL AC NO ON SW1 OFF - 24V ON - 12V + BAT --- Switch Detail ON Fig.
Fig. 3 - AL1012ULM CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuses with the same type and rating. Do not expose to rain or moisture. VR1 Door 15 Earth ground non power-limited Fig. 3a BAT FAIL AC FAIL Battery Connections non power-limited AC DELAY Battery and AC Supervision Circuit (power-limited).
Fig. 4 - AL1024ULM CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuses with the same type and rating (see marking on the board). Do not expose to rain or moisture. Fig. 4a + DC --- Earth Ground 4b 15A 32V - non power-limitedFig. NC C NO NC C NO 5A 250V Battery and AC Supervision Circuit (power-limited).
Maintenance: Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level (Output Voltage and Stand-by Specification Charts, pg. 4). Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery terminals and at the board terminals marked [+ BAT-- ] to ensure that there is no break in the battery connection wires.
Power Supply Board Terminal Identification Tables: Terminal Legend Function/Description L, G, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral. AL300ULM - 12VDC/24VDC @ 2.5 amp to MOM5 board (power-limited). AL400ULM - 12VDC @ 4 amp or 24VDC @ 3 amp to MOM5 board (power-limited). + DC – AL600ULM - 12VDC/24VDC @ 6 amp to MOM5 board (power-limited). AL1012ULM - 12VDC @ 10 amp to MOM5 board (power-limited). AL1024ULM - 24VDC @ 10 amp to MOM5 board (power-limited).
Typical Application Diagrams: (-) DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CONTROL DEVICE NEG (-) INPUT POS (+) (+) MOM5 module shown with wet and/or dry normally open trigger inputs (Non-Latching): EOL 2.2K (+) (-) N.C. INPUT FROM FACP OR ACCESS CONTROL DEVICE DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CONTROL DEVICE EOL 2.2K TRIGGER TRIGGER NEG (-) INPUT POS (+) Fig. 5 MOM5 module shown with wet and/or dry normally closed trigger inputs (Non-Latching): N.O.
Typical Application Diagrams (cont’d.): MOM5 module shown with with wet and/or dry normally open fire alarm trigger inputs (Latching with Manual Reset): (+) (-) MOM5 module shown with with wet and/or dry normally closed fire alarm trigger inputs (Latching with Manual Reset): DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT NEG (-) INPUT POS (+) NEG (-) INPUT POS (+) Fig. 8 (-) DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT TRIGGER TRIGGER EOL 2.2K (+) N.O.
Appendix A - UL Listed Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with AL300ULM, AL400ULM, AL600ULM, AL1012ULM, and AL1024ULM output.
AL1024ULM Battery Size Calculation Worksheet. A. AL1024ULM internal current consumption (stand-by) _______________ 0.13 A B. Load current consumption (stand-by) _______________ A C. Stand-by time required (hours) _______________ H D. Battery capacity required for stand-by (A+B)*C _______________ AH E. AL1024ULM internal power consumption (Alarm) _______________ 0.13 A F. Load current consumption (Alarm) _______________ A G. Alarm duration (Hours, example:15 Min = 0.
Enclosure Dimensions (BC300): AL300ULM, AL400ULM, AL600ULM 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) 1.40” (36mm) 4.85” (123mm) 4.85” (123mm) 1.40” (36mm) 1.20” (31mm) 3.25” (83mm) 1.20” (31mm) 0.75” (19mm) 12.5” (318mm) 11.0” (279mm) 1.20” (31mm) 0.75” (19mm) 0.9375” (24mm) 1.40” (36mm) 1.40” (36mm) 5.10” (130mm) 5.10” (130mm) 13.0” (330mm) 5.10” (130mm) 6.5625” (167mm) 0.9375” (24mm) 3.25” (83mm) 3.25” (83mm) 3.25” (83mm) 1.0” (25mm) 1.0” (25mm) 1.0” (25mm) M series 10.
Enclosure Dimensions (BC400): AL300ULMX, AL400ULMX, AL600ULMX, AL1012ULM, AL1024ULM 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 1.5” (38.1mm) 4.615” (117.22mm) 4.615” (117.22mm) 1.5” (38.1mm) 1.75” (44.45mm) 1.375” (34.925mm) 1.125” (28.575mm) 1.25” (31.75mm) 4.5” (114.3mm) 12.23” (310.64mm) 1.1” (27.94mm) 0.91” (23.114mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.1” (27.94mm) 1.25” (31.75mm) 0.91” (23.114mm) 2.0” (50.8mm) 1.5” (38.1mm) 15.5” (393.7mm) 2.0” (50.8mm) 5.0” (127.0mm) 5.0” (127.