Installation Guide

- 2 - M series
Input:
Power input 115VAC 60Hz (see reference chart above).
Fire Alarm Panel or Access Control System trigger
inputs. [NO] or [NC] supervised trigger input and
polarity reversal trigger input (4mA draw from FACP).
Output:
Five (5) individual power-limited class 2 outputs.
Current limit is 2 amp @ 12VDC or 24VDC
per output (12VDC only for AL1012ULM,
24VDC only for AL1024ULM).
Burglar Alarm Applications (UL 603)
AL300ULM and AL400ULM only:
12VDC = 10VDC-13.2VDC.
24VDC = 20VDC-26.4VDC.
Filtered and electronically regulated outputs.
Thermal and short circuit protection with auto reset.
Overload protection.
Output relay energizes when unit is triggered
(form “C” contact rated 1 amp @ 28VDC).
Battery Backup:
Built-in charger for sealed lead acid or gel type batteries.
Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when switching over to
battery backup.
AL300ULM, AL400ULM, AL600ULM and
AL1012ULM (Power Supply Board) maximum
charge current 0.7 amp.
AL1024ULM (Power Supply Board) maximum
charge current 3.6 amp.
AL300ULM, AL400ULM and AL600ULM enclosures
accommodate up to two (2) 12VDC/7AH batteries.
AL1012ULM should be fitted with
one (1) 12VDC/12AH battery.
AL1024ULM should be fitted with
two (2) 12VDC/12AH batteries.
Visual Indicators:
DC output LED indicator.
LEDs indicate condition of power outputs.
Power and input trigger LEDs.
Overview:
These multi-output access control power supply/chargers are specifically designed for use with access control systems and
accessories. These units convert a 115VAC, 60Hz input into five (5) individually protected 12VDC or 24VDC outputs (see
specifications). Each output will route power to a variety of access control hardware devices including Mag Locks, Electric
Strikes, Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes. Controlled trigger
input is achieved through normally open [NO] or normally closed [NC] supervised input or the polarity reversal from an
FACP (Fire Alarm Control Panel). A form “C” dry output relay enables HVAC Shutdown, Elevator Recall or may be used
to trigger auxiliary devices.
M Series Power Supply Configuration Reference Chart:
Altronix
Model
Number
12VDC Total
Output Current (amp)
24VDC Total
Output Current (amp)
Outputs
Class 2 Rated
Power Limited
115VAC 60Hz Input
(current draw/amp)
Power Supply Board
Input Fuse Rating
Power Supply Board
Output Fuse Rating
Agency Listings
UL Listings and
File Numbers
AL300ULM
2.5 2.5 5 Yes
3.5
amp
5A/
250V
15A/
32V
UL 1481 - UL Listed for Power Supplies for
Fire Protective Signaling Systems
UL 294 - UL Listed Access Control System Unit.
UL 603 - UL Listed for Burglar Alarms Systems.
UL 1069 - UL Listed Hospital Signaling and
Nurse Call Equipment.
---------------------------------
“Signal Equipment” Evaluated to CSA 22.2 N205-M1983
AL400ULM
4 3 5 Yes
3.5
amp
5A/
250V
15A/
32V
AL600ULM
6 6 5 Yes
3.5
amp
5A/
250V
-------------
AL1012ULM
10 ------------- 5 Yes
2.6
amp
5A/
250V
15A/
32V
UL File # BP617
UL 294 - UL Listed Access Control System Unit.
---------------------------------
“Signal Equipment” Evaluated to CSA 22.2 N205-M1983
AL1024ULM
------------- 10 5 Yes
4.2
amp
5A/
250V
15A/
32V
UL 1481 - UL Listed for Power Supplies for
Fire Protective Signaling Systems
UL 294 - UL Listed Access Control System Unit.
---------------------------------
“Signal Equipment” Evaluated to CSA 22.2 N205-M1983
Specifications: