Installation Instructions

LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF No DC output. Loss of AC. Discharged or no battery present.
Terminal Identification:
Terminal Legend Function/Description
AC/AC Low voltage AC input.
- DC +
12VDC @ 1.2A continuous supply current.
24VDC @ 750mA continuous supply current.
+ BAT - Stand-by battery connections. Maximum charge rate 300mA.
AC AC +DC -BAT +
AC
DC
FACTORY SET AT 12V
CUT J1 FOR 24V
CUT J2 FOR 6V
J1
J2
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: info@altronix.com. Lifetime Warranty, Made in U.S.A.
IIAL624 Kit - Rev. 090203 E18P
MEMBER