Installation Guide

- 10 - eFlow104N Series
NEC Power-Limited Wiring Requirements for eFlow104NX Models:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited
circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such
example of this is shown below. Your specific application may require different conduit knockouts to be used. Any
conduit knockouts may be used. For power- limited applications, use of conduit is optional. All field wiring connections
must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.
For Canadian installations use shielded wiring for all connections.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire, (Fig, 8a).
Fig. 8
Fig. 9a
*Outputs are non power-limited:
eFlow104NX, eFlow104NX8, eFlow104NX16.
Outputs are power-limited: eFlow104NX8D, eFlow104NX16D.
120VAC Input
60Hz
(non power-
limited)
Optional UL Listed
Battery Enclosure
(non power-limited)
Supervisory, Fire Alarm Interface
& Aux. output Connections
(power-limited)
Battery
Connections
(non power-
limited)
DC Output*
External
Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back
external jacketed
shield appro
x. 1/2”.
Wire
Insulation
Solid Copper
Conductors
Power
Distribution