Installation Guide

eFlow104N Series - 5 -
Terminal Identification:
Power Distribution Module
Terminal Legend
PD8UL/PD8ULCB
Terminal Legend
PD16W/PD16WCB
Function/Description
1P to 8P 1P to 16P Positive DC power outputs.
1N to 8N 1N to 16N Negative DC power outputs.
Fig. 1 - eFlow104N Board configuration
Trouble/Time Limited Warning of Stand-by Batteries:
For compliance with ULC S318-96, the Time Limited Warning circuit must be connected for local or remote annunciation
with an Amber or Red LED to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has
been depleted). Connect the circuit to the Batt Fail relay contacts to an appropriate input of a UL Listed Burglar Alarm
or Access Control Panel. The following figure shows the circuitry needed for local annunciation.
Fig. 2 - Battery trouble indication -
For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure.
Wire one leg of a UL Listed, power-limited power source to the indicating
lamp. Wire the second leg of the power source to the indicating lamp in
series with the battery fail relay contact terminals marked
[BAT FAIL - C, NO] (Fig. 2, pg. 5).