Power Supply/Chargers Installation Guide Models Include: eFlow3N/eFlow3NX - 2 amp @ 12VDC or 24VDC eFlow3N4/eFlow3NX4 - 2 amp @ 12VDC or 24VDC - Four (4) Fused Outputs eFlow3N4D/eFlow3NX4D - 2 amp @ 12VDC or 24VDC - Four (4) PTC Outputs Altronix Corp. 140 58th St. Brooklyn, NY Rev. 3NRP052213 More than just power.™ Installing Company: ______________________ Service Rep.
Overview: The eFlow3N power supply/chargers convert a 120VAC / 60Hz input to a 12VDC or 24VDC nominal output (see Power Supply Configuration Reference Chart and Specifications). eFlow3N eFlow3NX eFlow3N4 eFlow3NX4 eFlow3N4D eFlow3NX4D 10.1313.2 20.2826.39 10.1513.2 20.226.39 2A 10.1313.2 20.2826.39 10.1513.2 20.226.39 2A 9.7813.2 20.026.39 10.1513.2 20.226.39 2A 3 3.5A 5A/250V 3 3.5A 5A/250V 3 3.
Input: Specifications: Supervision (cont’d): • 120VAC, 60Hz. Output: • For output voltage and supply current, refer to eFlow3N series Power Supply Configuration Reference Chart, pg. 2. • Auxiliary Power-Limited output rated @ 1 amp (unswitched). • Over Voltage Protection. Battery Backup: • Built-in charger for sealed lead acid or gel type batteries. • Maximum charge current 1.54 amp. • Automatic switch over to stand-by battery when AC fails.
11. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching [Trigger EOL Shutdown] (Fig. 1e, pg. 5). 12. For Access Control Applications: mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right side (Fig. 4, pg. 7 or Fig. 6, pg. 9). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device.
Terminal Identification: Power Distribution Module Terminal Legend Function/Description PD4UL/PD4ULCB 1P to 4P Positive DC power outputs. 1N to 4N Negative DC power outputs. Fig. 1 - eFlow3N Board configuration OPEN --- 24V CLOSED --- 12V AC1 5A 250V L G 1a N AC FAIL BAT FAIL --- DC + 1h --- BAT + 1i 1g AC DELAY SHUTDOWN O N NC C NO NC C NO AC DC 1b 1 min. 2 hr.
Power Distribution Module(s): Fig. 3a - PD4UL Power Distribution Board Fig. 3b - PD4ULCB - Power Distribution Board Replace fuses with the same type and rating 3.5A, 250V.
Fig. 4 - eFlow3N configuration Edge of Enclosure Enclosure to Access Control Panel or U.L.
NEC Power-Limited Wiring Requirements for eFlow3N Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
Fig. 6 - eFlow3NX configuration Edge of Enclosure Enclosure Battery & AC Supervision Circuit (power-limited) power-limited Sentrol model # 3012 Tamper Switch or equivalent (Not Included) 120VAC power mains (non power-limited) Class 1 to Access Control Panel or U.L. Listed Reporting Device L AC1 AC DC AC DELAY SHUTDOWN AC FAIL BAT FAIL G C NO NC 2 hr. 1 min.
NEC Power-Limited Wiring Requirements for eFlow3NX Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
Enclosure Dimensions (BC300): eFlow3N, eFlow3N4, eFlow3N4D 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) 1.40” (36mm) 4.85” (123mm) 4.85” (123mm) 1.40” (36mm) 1.20” (31mm) 3.25” (83mm) 1.20” (31mm) 0.75” (19mm) 12.5” (318mm) 11.0” (279mm) 1.20” (31mm) 0.75” (19mm) 0.9375” (24mm) 1.40” (36mm) 1.40” (36mm) 5.10” (130mm) 5.10” (130mm) 13.0” (330mm) 5.10” (130mm) 6.5625” (167mm) 0.9375” (24mm) 3.25” (83mm) 3.25” (83mm) 3.25” (83mm) 1.0” (25mm) 1.0” (25mm) 1.
Enclosure Dimensions (BC400): eFlow3NX, eFlow3NX4, eFlow3NX4D 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 1.5” (38.1mm) 4.615” (117.22mm) 4.615” (117.22mm) 1.5” (38.1mm) 1.75” (44.45mm) 1.375” (34.925mm) 1.125” (28.575mm) 1.25” (31.75mm) 4.5” (114.3mm) 12.23” (310.64mm) 1.1” (27.94mm) 0.91” (23.114mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.1” (27.94mm) 1.25” (31.75mm) 0.91” (23.114mm) 2.0” (50.8mm) 1.5” (38.1mm) 15.5” (393.7mm) 2.0” (50.8mm) 5.0” (127.0mm) 5.0” (127.0mm) 1.1” (27.
Appendix A - UL Listed Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with eFlow3N output.
Notes: - 14 - eFlow3N Series
Notes: Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 website: www.altronix.com, e-mail: info@altronix.com, Made in U.S.A.
Power Supply/Chargers Operating Guide Models Include: Input 120VAC, 60Hz Model Output 12VDC 24VDC PowerLimited Auxiliary Power-Limited Output (unswitched) Ripple Voltage 3 1 amp 960mV eFlow3N, eFlow3N4, eFlow3N4D 3.5 amp 2 amp 2 amp eFlow3NX, eFlow3NX4, eFlow3NX4D Overview: The eFlow3N series power supply/chargers convert a 120VAC, 60Hz input, to a 12VDC or 24VDC output. Stand-by Specifications: Battery Fire Applications 24 hr. Stand-by/5 min. Alarm Access Control Applications Stand-by 0.