Data Sheet

Input:
120VAC, 60Hz, 3.5 amp.
Input fuse: 5A/250V.
Output:
Eight (8) PTC protected power-limited outputs.
12VDC or 24VDC selectable output.
12VDC or 24VDC @ 4.0 amp supply current.
Outputs are rated @ 2 amp.
Auxiliary power-limited output
rated @ 1 amp (unswitched).
Overvoltage protection.
Battery Backup:
Built-in charger for sealed lead acid or gel type batteries.
Maximum charge current 1.54 amp.
Automatic switch over to stand-by battery when
AC fails. Transfer to stand-by battery power is
instantaneous with no interruption.
Supervision:
AC fail supervision (form “C” contacts).
- Notification trigger is selectable for
30 seconds (factory set) or 2 hours.
Battery fail and presence supervision
(form “C” contacts).
Low power shutdown. Shuts down DC output terminals
if battery voltage drops below 71-73% for 12V units
and 70-75% for 24V units (depending on the power
supply). Prevents deep battery discharge.
Fire Alarm Disconnect:
Supervised Fire Alarm disconnect (latching or
non-latching) 10K EOL resistor. Operates on a
normally open (NO) or normally closed (NC) trigger.
Electrical:
Operating temperature: 0º C to 49º C ambient.
• BTU/Hr.:
12VDC: 24.57 BTU/Hr.
24VDC: 49.15 BTU/Hr.
System AC input VA requirement: 420VA.
Visual Indicators:
Green AC Power LED indicates 120VAC present.
AC input, DC output, and Battery LED indicators.
Additional Features:
Short circuit and overload protection.
Unit is complete with power supply, enclosure,
battery leads and cam lock.
Mechanical:
Enclosure Dimensions (H x W x D approx.):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
- Accommodates up to two (2) 12VDC/12AH batteries.
Product weight (approx.): 8.55 lbs. (3.88 kg).
Shipping weight (approx.): 9.6 lbs. (4.35 kg).
Specifications
eFlow4NX8D is a power supply/charger that converts a 120VAC, 60Hz input
into eight (8) PTC protected 12VDC or 24VDC power-limited outputs.
eFlow4NX8D
Power Supply/Charger
Rev. DSeFlow4NX8D_05132015
Overview
Agency Approvals
UL 294 UL Listed for Access Control
System Units.
UL 603 UL Listed for Power Supplies
for Use with Burglar-Alarms
Systems.
UL 1481 UL Listed for Power Supplies
for Fire Protective Signaling
Systems.
ULC-S318-96 - Power Supplies for
Burglar Alarm Systems. Also suitable for
Access Control.
CSFM - California State Fire
Marshal Approved.
Altronix Corp.
140 58th St. Brooklyn, NY
CE - European Conformity
eFlow4NX8D

Summary of content (2 pages)