Please be sure to visit altronix.com for latest firmware and installation instructions Network Power Distribution Module Installation and Programming Manual LINQ8PD - Network Power Distribution Module - Eight (8) Fused Outputs LINQ8PDCB - Network Power Distribution Module - Eight (8) PTC Outputs DOC#: LINQ8PD Rev. 020916 More than just power.
Overview: Altronix LINQ8PD(CB) network power distribution module facilitates monitoring, reporting and control of one (1) or two (2) low voltage AC or supervised DC power supply/chargers over the network. Reports diagnostics via Email/SNMP notifications greatly reducing system downtime and eliminating unnecessary service calls. LINQ8PD(CB) retrofits with most currently installed multi-output power supply/chargers.
Terminal/Connector Identification: A B C D E F G H I A B C D E F G H I J A B C D E F G H I J K J K L K L M L M N M N O P Q N O P Q R R S O P Q R S T Terminal/Legend Description A B C D E F G H IFACP J Kreset. L M N O P Q R S T U V GND, RESET Q R B C D E F G H I JConnects K L Mto N O or P next S T U V GND, FACP EOL EOL LINQ8PD(CB). C D E F-- G H I J KFACP L MEOL, N Oor P R S T U V + RET nextQ LINQ8PD(CB). D E F -G IN H + I J K LWet M input N Ofrom P QFACP R S+.
Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only and should be installed by qualified personnel. 1. Disconnect the AC mains and batteries (if used) from the power supply(ies) before connecting the LINQ8PD(CB) 2. Mount LINQ8PD(CB) into position and secure with mounting screws.
Please be sure to visit altronix.com for latest firmware and installation instructions. Establishing Network Connection: Network Setup - Altronix Dashboard USB Connection The USB connection on the LINQ8PD(CB) is used for Network and Trap Receiver configuration only. When connected to a PC via the USB cable the LINQ8PD(CB) will receive power from the USB port allowing programming of the LINQ8PD(CB) prior to being connected to the power supply. 1.
Field Name Description Subnet Mask When operating in DHCP the router will assign the subnet mask values. Gateway Enter the TCP/IP gateway of the network access point (router) being used. Enables standard remote access and monitoring. Enter the port number assigned to the LINQ8PD(CB) module by the network administrator. HTTP Port Default Port setting 80.* Enables secure remote access and monitoring. Enter the port number assigned to the LINQ8PD(CB) module by the network administrator.
1. Network setup: Click [Network Settings] tab. This will open the Network Setting screen. In this screen the MAC Address of the LINQ8PD(CB) module will be found along with the programming fields for the Network Settings, Trap Receiver Settings, SNMP Port Settings and Email Settings. Network Settings (Fig. 3a, pg. 7): In the IP Address Method field select the method that the IP Address for the LINQ8PD(CB) will be obtained “Static” or “DHCP” then follow the appropriate steps. Fig.
Trap Receiver Settings (Fig. 3b, pg. 7): a. Enter up to five SNMP trap receiver IP addresses. When accessing the LINQ8PD(CB) remotely check with the network administrator for proper configuration. b. Click [Submit Trap Receiver IP Settings] button, a dialog box will display “New Trap Receiver IP settings will take effect after the server is rebooted” click “OK”. SNMP Port Settings (Fig. 3c, pg. 7): SNMP uses the default port 161 for general SNMP messages and port 162 for SNMP trap messages.
Device Management Interface 2. Setup (Fig. 4, pg. 9): Note: If the Altronix Dashboard is being used for LINQ8PD(CB) setup, refer to the Folder and Device configuration section in the Altronix Dashboard setup/user manual. Click on [Setup] tab. The LINQ8PD(CB) setup page will open. This page is used to configure all operating functions of the LINQ8PD(CB). Fig.
Battery Monitor Configuration (Fig. 7, pg. 10): The LINQ8PD(CB) displays the real time battery health. Select Battery Capacity Battery Charge Level Max. Battery Discharge Current Description Enter the battery rating in amp hours. Enter the estimated percentage charge level of the Battery at the time of installation. Enter the high current limit to be drawn from the battery in the event of a power failure. If this limit is exceeded an SNMP trap message and/or email notification will be generated.
FACP Trigger (Fig. 8, pg. 10): From the pull down menu select how the output will operate when the FACP input is triggered. FACP Trigger Setting Function/Description Inactive The selected output will not switch when the FACP input is triggered. Non Latching The selected output will switch when the FACP input is triggered and reset when the FACP trigger input is returns to a non-triggered state. The selected output will switch to a latched position when the FACP input is triggered.
SSL Status: Certificate Status (Fig. 9b, pg. 11): Message Certificate OK Bad Certificate No Certificate Key Status (Fig. 9b, pg. 11): Descriptions Valid SSL Certificate. Invalid SSL Certificate. A Valid SSL Certificate has not been loaded. Message Key OK Bad Key No Key Descriptions Valid SSL Key. Invalid SSL Key. A valid SSL Key has not been loaded. SSL State: The SSL of the LINQ8PD(CB) can be turned on and off by clicking [Turning SSL On/Turning SSL Off] button.
Fig. 11 Device Management Interface Status Setup Network Settings Security Settings Events Log Help v1.99.22 Status Monday, Sept. 21 2015 [2:30 pm] Site ID: LINQ8 Minimize LINQ8PD ID: LINQ8 DEV PS1 Output Voltage PS1 Load PS2 Output Voltage PS2 Load Output A 27.5 VDC 2.55 A 13.7 VDC 2.55 A FACP Status Reset Tamper Status Temperature B Normal Not Triggered 31 C AC Status Battery Status Battery Capacity Battery Voltage C Normal Normal 7 AH 27.
Notes: - 14 - LINQ8PD/LINQ8PDCB
Notes: LINQ8PD/LINQ8PDCB - 15 -
Notes: Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 website: www.altronix.com, e-mail: info@altronix.com. Lifetime Warranty, Made in U.S.A.