Installation Instructions

- 2 - LINQ8PD/LINQ8PDCB
Overview:
Altronix LINQ8PD(CB) network power distribution module facilitates monitoring, reporting and control of one (1) or two (2) low voltage AC or supervised DC power supply/chargers
over the network. Reports diagnostics via Email/SNMP notifications greatly reducing system downtime and eliminating unnecessary service calls. LINQ8PD(CB) retrofits with most
currently installed multi-output power supply/chargers.
Specifications:
Terminal/Connector Identification:
Input Power:
Input1/Input2: 12VAC-28VAC @ 12.5 amp each or
12VDC/28VDC @ 12.5 amp each
Note: Do connect AC and DC simultaneously to
INP1 and INP2
Outputs:
Eight (8) fused or PTC protected outputs:
- LINQ8PD: Blade fuses are rated 3 amps
- LINQ8PDCB: PTCs are rated 2.5 amps
Power output(s) can be locally or remotely controlled
Surge Suppression
Status Monitoring:
Power Supply(ies) output voltage and load
Voltage and load of each output
FACP trigger and reset status
Unit temperature (Celsius)
Power Supply AC and Battery status
Battery health
Programming Features:
Power Supply(ies) voltage and load limits (High/Low)
FACP trigger type (wet or dry-N.O./N.C.)
Input Function (FACP reset/tamper)
Output Reset Trigger (N.O./N.C.)
Battery Monitor Configuration:
- Capacity
- Charge Level
- Max. Charge and Discharge Current
- Service Date
Configurable Output Relay(s)
Individual Output Configuration:
- Device ID
- Voltage and Current Limits (High/Low)
- FACP Trigger Setting (latching/non-latching/inactive)
- Battery Backup
Network Security:
Secure Socket Layer (SSL)
Reporting:
SNMP trap messages.
E-mail notifications
Event Log tracks history
Fire Alarm Interface:
Supervised FACP disconnect (Latching or Non-Latching)
FACP reset (N.C. or N.O.)
Environmental:
Operating temperature: -20° to 49°C (-4° to 120.2°F).
Storage temperature: -30ºC to 70ºC (-22º to 158ºF).
Mechanical:
Board Dimensions: 5.5”L x 3.625”W x 0.96”H
(139.7mm x 92.07mm x 24.38mm)
Product weight (approx.): 0.4 lbs. (0.18kg)
Shipping weight (approx.): 0.7 lbs. (0.32kg)
--
NC C NC C
FACP
AC
BAT
BAT LOCAL
Altronix Corp.
Brooklyn, NY 11220
LINQ8PD
FACP RLY 2
FACP RLY 1
RET+
RET --
FACP IN+
FACP IN --
FACP EOL
--
INP1
+
~~
--
INP2
+
~~
-- OUT1 +-- OUT2 +-- OUT3 +-- OUT4 + -- OUT5 +-- OUT6 +-- OUT7 +-- OUT8 +
GND
RESET
GND
FUSE OUT8
AC Fail Battery Fail
FUSE OUT7
FUSE OUT6
FUSE OUT5
FUSE OUT4
FUSE OUT3
FUSE OUT2
FUSE OUT1
Fuse Battery
UPLINK
DOWNLINK
<
INP1 OFF INP2
>
+ BAT IN -
DRY Inputs
+ BAT OUT -
BAT AC
NO C NO C
A B C D E F G
I
J
K
L
M
N
O
R
P
S
T
U
V
Q
H
15
15
15 333333 33
ON
1
EOL OFF
LINQ8PD - Fig. 1