Installation Instructions

R1224DC16CBV Installation Guide - 3 -
11. All four (4) power LEDs on the faceplate will illuminate when AC power is present (Fig. 3a, pg. 4).
Note: If the power LEDs are not illuminated the cause may be due to the following:
a. AC mains fail.
b. Illuminated master power disconnect circuit breaker is OFF or tripped.
If one (1) or more power output PTCs are tripped due to a short circuit or overload condition follow
the steps below to reset PTC:
1. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 3d, pg. 4).
2. Eliminate the trouble condition (short circuit or overload).
3. Allow 1 minute for PTC to cool off (reset).
4. Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 3d, pg. 4).
5. All power LEDs will illuminate (Fig. 3, pg. 4).
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
Mounting Options:
Rack Mount Installation
1- Install mounting brackets (A) on the left and right side of rack chassis using the two (2) flat head screws
(B) (included) (Fig. 1a).
2- Place unit into desired EIA 19” rack position and secure with mounting screws (not included) (Fig. 1b).
Fig. 1 1a Top 1b Top
Shelf Installation
1- Position and affix rubber pads (C) (included) at each corner on the bottom of the unit (Fig. 2).
2- Place unit in desired location.
Fig. 2
A
B
Front Front
C
B
A
C
Mounting Hardware
(Included):
Four (4) mounting brackets.
Eight (8) flat head screws
for mounting brackets.
Four (4) rubber pads.
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user
to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of
sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of impor-
tant operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure.
There are no user serviceable parts inside.
Refer servicing to qualified service personnel.