Technical information

INSTALLATION
22
Use the table below to determine the number of pipe supports you need to install.
Distance (ft.) Number of Pipe Supports
16 2
32 3
48 5
64 7
80 9
C.3.1. Installation At The Same Level
If the condensing unit is going to be installed at the same level with the cabinet, follow the instructions in the
DRAWING C.3.1.1
DRAWING C.3.1.1
C.3.2. Installation At Different Levels
If the remote condensing unit is installed at a higher level than the cabinet (DRAWING C.3.1.2) insert a siphon in
the return line at every 6 ft. of difference in height. If the remote condensing unit is installed at a lower level than the
cabinet (DRAWING C.3.1.3) it is not necessary to insert any siphons.
DRAWING C.3.1.2
Insert a siphon at the beginning (a) and at the end (b) of each riser