User Manual English APC Smart-UPS® XL SURT192RMXLBP2 SURT192XLBP2 Stack/Rack-Mount 6U External Battery Pack 990-2485 03/2007
Introduction About this unit The American Power Conversion (APC®) SURT192RMXLBP2 external battery pack (XLBP) connects to an APC Smart-UPS® RT greater than 10 kVA. Together these units provide extended protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS and the XLBP together provide continuous power from the batteries until utility power returns to safe levels or the batteries are fully discharged.
Specifications Environmental Specifications Temperature Operating Storage 32° to 104° F (0° to 40° C) 5° to 113° F (-15° to 45° C) charge the UPS battery every six months 86° to 158° F (30° to 70° C) charge the UPS battery every three months Maximum Elevation Operating Storage 10,000 ft (3,000 m) 50,000 ft (15,240 m) Humidity 0 to 95% relative humidity, non-condensing This unit is intended for indoor use only. Select a location sturdy enough to handle the weight.
Installation Stack configuration Always place the UPS above the XLBP in a stack configuration. Total stack configuration height is recommended NOT to exceed 18U. This is the equivalent of two XLBPs and one UPS. Four screws must be used to secure each tie bracket to the units, (see diagram). For detailed instructions on installing batteries, the battery doors, and bezels, refer to the Rack-mount configuration section of this manual.
Install units in rack Secure the UPS and the XLBP in the rack using the cage nuts and ornamental screws included in the package. 7 holes Four ornamental screws and two cage nuts must be used to secure each unit. A cage nut must be used in the top hole of each rack-mount bracket when securing the unit in the rack. 4x 7 holes The bottom hole of each rack-mount bracket can be secured using an ornamental screw in the threaded hole.
Connect UPS and XLBP(s) Connect the ground wires as shown. There are two ground connecting locations on each unit. Remove the battery connector covers on UPS and XLBP(s). Ground Ground Connect the batteries as shown. Ground UPS XLBP with PDU installed Rotate battery connector covers Re-install the battery connector covers on UPS and XLBP(s).
Operation Battery LED The battery LED is located on the front bezel of the XLBP. During normal operation the LED is not illuminated. On start-up the XLBP LED may illuminate and blink within the first minute. The LED should then extinquish. LED Activity Possible Cause XLBP LED illuminates briefly ~ On start-up the XLBP LED may illuminate and blink within the first minute. ~ The XLBP is establishing communication with other components of the system.
Maintenance and Service Information Replace battery modules This unit has easy-to-replace, hot-swappable battery modules. Replacement is a safe procedure, isolated from electrical hazards. You may leave the unit and connected equipment on during the replacement procedure. Once the batteries are disconnected the connected equipment is not protected from power outages. Refer to the appropriate replacement battery user manual for battery module installation instructions. See your dealer or contact APC at www.
Two-Year Warranty The limited warranty provided by American Power Conversion (APC®) in this statement of Limited Factory Warranty applies only to products you purchase for your commercial or industrial use in the ordinary course of your business. Terms of warranty APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase.