ASYSTAT300C, ASYSTAT302C Deluxe Programmable Heat-Cool Thermostats OWNER’S GUIDE Pub. No. 12-5027-01 (ASYSTAT300C shown) 1 Pub. No.
TABLE OF CONTENTS CUSTOMIZING YOUR THERMOSTAT ............................................................................................................. 5 Program Options Set-Up by Your American Standard Dealer ........................................................................... 5-6 GETTING AROUND THE KEYBOARD ............................................................................................................. 7-8 FEATURES ...................................................................
Filter Indication .............................................................................................................................................. Setting or Resetting Filter Indication Timer ................................................................................................... 25 26 PROGRAMMING YOUR THERMOSTAT .......................................................................................................... Clock .........................................................
TROUBLESHOOTING ....................................................................................................................................... 59 DEFINITIONS .................................................................................................................................................... 62 INDEX ................................................................................................................................................................
CUSTOMIZING YOUR THERMOSTAT Program Options Set Up by Your American Standard Dealer Your American Standard dealer has programmed your thermostat using the options checked below. For example, your thermostat displays temperatures in degrees Fahrenheit if the checkbox next to Fahrenheit (°F) is checked. Contact your American Standard dealer to reprogram any of the options listed. NOTE: If no options are checked, those listed in the first column are the factory settings on your thermostat.
Comfort-R™ Control Adaptive Intelligent Recovery™ Control Cooling Droop Temperature Display Clock Format System Setting (Heating and Cooling Setting) ❑ ❑ Off On ❑ ❑ On Off (Conventional recovery) ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Off Centigrade (°C) 24-Hour Clock Format Manual Only (You select Heat, Cool or Off.) Outdoor Temperature Display ❑ ❑ Programming ❑ On Fahrenheit (°F) 12-Hour Clock Format Auto/Manual (System automatically selects Heat or Cool; You can select Heat, Cool or Off.
GETTING AROUND THE KEYBOARD The keyboard is located behind the thermostat cover. Three frequently used keys are located next to the display (Increase temperature setting, Decrease temperature setting, and Information key). The thermostat displays important information such as day, time, schedule period, temperature, filter indicator, system and fan operation. WHAT'S THE ROOM TEMPERATURE? WHAT TIME IS IT? DISPLAY IS BACKLIT FOR EASY READABILITY WHEN A KEY IS PRESSED.
NO NEED TO WORRY ABOUT PRESSING THE WRONG KEY! RUN PROGRAM, RETURN TO NORMAL OPERATIONS, OR UNDO LAST ACTION. SET CURRENT DAY AND TIME (INITIALLY AND AFTER EXTENDED POWER OUTAGES). Run Program HOLD MODE: OVERRIDE NORMAL PROGRAMMING OPERATION, OR GO INTO VACATION MODE! SET CURRENT OR PROGRAM DAY EASILY CHANGE BETWEEN STANDARD AND DAYLIGHT SAVINGS TIME Set Current Day/Time Leave Wake Heat/Cool Settings Day Daylight Time Return Sleep SELECT SYSTEM OPERATION (HEAT, COOL, OFF, AUTO).
FEATURES • • Worry-free programming. • Comfort-R Comfort Enhancement Process—a unique American Standard feature. • Adaptive Intelligent Recovery Control for comfort and energy savings. • Wake, Leave, Return and Sleep at the comfort level you select. • Customize the program schedule—program your own schedule to fit your needs. • Continuous comfort and energy savings— adjust the schedule as often as you like. • Temporary schedule override—set the thermostat higher or lower for the current program schedule.
FEATURES YOU’LL WANT TO KNOW MORE ABOUT The Comfort-R™ system is specifically designed to enhance the moisture removal process of your air conditioning system and to make the air drier. This system is so unique, it received a patent from the U.S. Patent Office. During times of high relative humidity, as well as during mild weather, the Comfort-R system increases the moisture removal ability of your airconditioning system.
Adaptive Intelligent Recovery Control these three things, Adaptive Intelligent Recovery™ control gradually changes the temperature from the energy savings setting to the comfort setting (for example, from a heating temperature of 62° at night to 70° in the morning). Your Thermostat Senses Temperature More Like You Do Your new thermostat is so smart, it’s almost human.
After installation or new schedule programming, your thermostat learns from experience. How? Each day it checks how closely it hit the recovery target (for example, 70° at 6:00 AM) and adjusts the next day’s recovery start time accordingly. After four to eight days, the thermostat has adjusted to local weather, your lifestyle, the construction of your home, and your heating and cooling system. Your new thermostat saves energy and keeps you comfortable at the same time.
System Heat AM Fan Mon Wake Room Auto TEMPERATURE System Heat Recovery AM Fan Room Mon Sleep Auto System Heat Recovery AM Fan Room Mon Sleep Auto System Heat Recovery AM Fan Room Mon Sleep Auto TIME THE THERMOSTAT USES THE SAME SCHEME TO RETURN GRADUALLY TO LOWER COMFORT TEMPERATURE DURING THE COOLING SEASON. 13 M14562 Pub. No.
NEAT STUFF YOU’LL BE USING OFTEN Setting Temporary Temperatures If your thermostat is set for 7-Day or 24-Hour Operation, you can override the current schedule period and change the temperature setting until the next schedule period, or change the temperature setting while you are on vacation. You can also change the temperature setting indefinitely. Changing Temperature Setting Until the Next Schedule Period NOTE: This feature does not apply to Constant Temperature Setpoint Programming.
The temporary temperature setting you select displays for approximately 3 seconds. The display reads Temporary until the next period begins, or you cancel the Hold. Run Program IMPORTANT To cancel the Hold before the designated time, press Run Program. System Heat Temporary AM Fan Mon Heat Auto M14564 After selecting a temporary setting, display reads Temporary until canceled. Example displays shows temporary heat setting of 70° at 6:00 AM.
Changing Temperature Setting Indefinitely NOTE: This feature does not apply to Constant Temperature Setpoint Programming. NOTE: The current time does not display while in this mode. Hold Temp 1. Press Hold Temp once. Setting System Heat Fan Heat Auto M14565 Pressing Hold Temp once displays the thermostat in Hold mode. Example displays shows temporary heat setting of 60°. 16 Pub. No.
2. Press Increase ▲ or Decrease ▼ to change the temperature setpoint, if desired. Setting System Heat Fan Heat Auto M14566 By pressing the Temperature keys, you can select a temporary temperature. This temperature setting remains until the hold is canceled. Example displays shows heat set to 61°. Heat/Cool Settings 3. Press Heat/Cool Settings to change between heat and cool settings. Setting System Heat Fan Cool Auto M14567 Pressing Heat/Cool Settings displays the other temperature setpoint.
4. Press Increase ▲ or Decrease ▼ to adjust temperature settings. Setting System Heat Fan Cool Auto M14568 Pressing the Temperature keys changes the temporary temperature. Example displays shows temporary cooling setting of 80°. NOTE: The display changes from the setpoint to the room temperature after approximately 3 seconds. Run Program IMPORTANT To cancel the Hold, press Run Program. 18 Pub. No.
Vacation Mode NOTE: This feature does not apply to Constant Temperature Setpoint Programming. Hold Temp 1. Press Hold Temp twice. Setting Cool M14569 Pressing Hold Temp twice displays the thermostat in Vacation mode. Example displays shows temporary heat setting of 60°. 19 Pub. No.
Time 2. Press Time ▲ or Time ▼ until the desired number of days displays (1 to 255 days). System Heat Fan Auto M14570 By pressing the Time keys, the number of vacation days is selected. Example displays shows 18 vacation days. 3. Press Wake, Leave, Return or Sleep to select the period the Hold will stop. Wake Leave Return System Heat Sleep Fan Auto M14571 In this example, the Hold will stop after the 18th day at the beginning of the Return period. 20 Pub. No.
4. Press Increase ▲ or Decrease ▼ to adjust the temperature setting, if desired. System Heat Fan Auto M14572 By pressing Temperature keys, a new hold temperature is selected. Example display shows temporary heat setting of 55°. NOTE: Only the heating temperature is used when the System is set to Heat. Similarly, only the cooling temperature is used when the System is set to Cool. The thermostat uses both the heating and cooling temperatures when the System is set to Auto. Heat/Cool Settings 5.
Run Program IMPORTANT To cancel the Hold before the designated time, press Run Program. Pressed the wrong key? Want to start over? Don’t worry! You can always press Run Program to return display to normal. 22 Pub. No.
Information Key System Heat The Information key provides information at your fingertips.
Displaying Current Settings Press twice to check the current temperature setpoint. Press three times to check the temperature setpoint of the mode not currently in use. Setting Cool NOTE: Without outdoor temp. sensor, press once to display current setpoint; twice for opposite setpoint. M14575 Pressing key twice displays current setpoint. Example displays shows cooling setpoint of 75°.
Filter Indication Your thermostat monitors the time the fan is running and lets you know when to replace the filter, based on the number of fan run-time days you select. Upon expiration, the thermostat displays Filter and the backlight flashes during the Wake and Return modes. System Em Heat AM Filter Tue Wake Fan Room DST FILTER EXPIRATION INDICATOR Auto M14576 To temporarily cancel the flashing display, press 25 Pub. No.
Setting or Resetting Filter Indication Timer Your thermostat comes preset to the 30-day setting. To change this setting, or reset after filter expiration, follow these instructions: Filter Setting 1. Press Filter to enter the Filter mode. Filter M14577 Pressing the Filter key displays filter information. In this example, current fan run time is 5 days and the filter is set to expire in 30 days. Filter 2. Press and hold Filter for at least 3 seconds to reset fan run time to zero.
3. Press Time ▲ or Time ▼ until the desired number of days displays (0, 7, 14, 21, 30, 45, 60, 90, 120, 180, 270, or 360). Run Program 4. Press Run Program to return to normal operation. IMPORTANT To track the time the fan is running, you must select a setting other than 0. If the setting is 0 days, the display will always show “0 Days; 0 Setting” when Filter is pressed. 27 Pub. No.
PROGRAMMING YOUR THERMOSTAT Clock Setting Current Day and Time IMPORTANT Always press the keys with your fingertip or similar blunt tool. Sharp instruments like pens and pencil points will damage the keyboard. On initial power up or after an extended power loss, 1:00 PM flashes on the display until a key is pressed. Wait Pressed the wrong key? Want to start over? System Set Day/Time Cool PM Don’t worry! You can always press Fan Mon Room Run Program Auto M14579 to return display to normal.
Set Current Day/Time 1. Press Set Current Day/Time. PM Mon M14580 Pressing Set Current Day/Time displays the information shown. 2. Press Day until the current day displays. Day NOTE: Mon = Monday, Tue = Tuesday, Wed = Wednesday, Thu = Thursday, Fri = Friday, Sat = Saturday, Sun = Sunday. PM M14581 By Pressing Day, you can set the current day. Example display shows Tuesday. 29 Pub. No.
3. Press Time ▲ or Time ▼ until the current time displays. Time AM NOTE: Tapping Set Current Day/ Time advances the time in one-hour increments. M14582 By Pressing Time, you can set the current time. Example display shows 8:15 AM. Daylight Time NOTE: If the current time is Daylight Savings Time, press Daylight Time until DST displays. AM M14583 By Pressing Daylight Time, you can set Daylight Savings Time. Run Program 4. Press Run Program to return to normal operation. 30 Pub. No.
Setting System and Fan The system default setting is Heat and the fan default setting is Auto. Use the System and Fan keys to change the settings. The fan settings can be set for each schedule period individually. The system selection is for all the schedule periods. Set System System Fan Press System until the desired system displays (Heat, Off, Cool, or Auto). Heat: The thermostat controls the heating. Off: Both the heating and cooling are off. Cool: The thermostat controls the cooling.
7-Day Program and Operation Your thermostat comes preset for 7-Day Operation unless otherwise noted on page 6. After reviewing the options following this section, you may find that 24-Hour Operation or Constant Temperature Setpoint Programming is better for you and your family. If so, please consult your American Standard dealer or service technician.
Table 1. 7-Day Preprogrammed Schedule.
Customizing Your Own 7-Day Schedule Before starting the programming procedure, use Tables 2 and 3 to organize your schedule. The preprogrammed schedule is shown in Table 1. Four time periods are available for each day of the week – WAKE, LEAVE, RETURN, and SLEEP. A Word About Power Outages Don’t worry! Your thermostat retains the schedule (preprogrammed or your own) for the life of the product. The clock and day information is retained for a minimum of ten minutes during a power outage.
Instructions 1. Write in the time you want each schedule period to begin. 2. Write in the heating temperature (H) and cooling temperature (C) you want for each period. 3. Circle the fan operation you desire for each period. 4. Begin with Programming the First Day! Pressed the wrong key? Want to start over? Don’t worry! You can always press Run Program to return display to normal. 35 Pub. No.
Table 2. Your 7-Day Schedule.
Table 3. An Extra 7-Day Schedule.
Programming the First Day To modify the preprogrammed schedule, start by programming the Wake time and temperature and fan operation for any one day: NOTE: This schedule follows the current day and time you set in the section Setting Current Day and Time and the Heat or Cool setting and Fan setting you selected in the section Setting System and Fan. 1. Press Wake. Setting Set Program Wake System Heat AM Fan Tue Wake Heat Auto M14586 By pressing Wake, you enter the program mode.
Day 2. Press Day until the desired day displays. Setting Set Program System Heat AM Fan Mon Wake Heat Auto M14588 By pressing Day, you select the day to program. Example display shows Monday is selected and ready to program. 3. Press Time ▲ or Time ▼ until the desired Wake time displays. Time Setting Set Program System Heat AM NOTE: The program times are in fifteen-minute intervals. (Example: 8:00, 8:15, 8:30).
4. Press Increase ▲ or Decrease ▼ until the desired Wake temperature displays. NOTE: The setpoint temperature range is 55 to 85°F (13 to 29°C) for heating and 65 to 99°F (18 to 37°C) for cooling. Setting Set Program System Heat AM Fan Mon Wake Heat Auto M14590 By pressing Increase L or Decrease M, you select the temperature for the Wake period. Example display shows the heating Wake period set for 68°. Fan NOTE: Press Fan to modify fan operation.
Heat/Cool Settings 5. Press Heat/Cool Settings to make selections for the opposite system setting (either Heat or Cool). Setting Set Program System Heat AM NOTE: If your system is set for Heat, only Fan the heating temperature will be used. Mon Auto Cool Wake Similarly, if your system is set for Cool, only the cooling temperature M14591 will be used. If your system is set for By pressing Heat/Cool Settings, you select the cooling system (if you already set the heating temperature).
7. Press Leave, Return or Sleep and repeat steps 3, 4, 5 and 6 for programming the rest of the day. The day is now programmed (first day of a seven-day schedule). Leave Return Sleep IMPORTANT Repeat steps 1 through 7 for each day of the week that has a different schedule from the first day. Or, refer to the section Copying a Day to copy any programmed day to another. Run Program 8. Press Run Program to return to normal operation.
Copying a Day NOTE: The copy feature applies only to 7-Day Operation. The thermostat must be in the program mode to use the copy feature. Go to step 2 if the thermostat is already in the program mode (Set Program displays in upper left corner). 1. Press Wake, Leave, Return or Sleep to enter program mode. Wake Day Leave Return Sleep 2. Press Day to select the day to copy from.
Copy 3. Press Copy. Mon M14594 By pressing Copy, you copy a day’s schedule into memory. Example display shows Monday’s schedule has been copied into memory. Day 4. Press Day until the day to be copied to is displayed. Mon Wed M14595 By pressing Day again, you select which day to copy to. Example display shows Monday and Wednesday. Since Monday was already selected, Monday’s schedule will be copied to Wednesday. 44 Pub. No.
Copy 5. Press Copy. NOTE: donE displays for two seconds before the normal display returns. M14596 By pressing Copy again, you complete the copy command. Example display shows donE. Monday’s schedule was successfully copied to Wednesday (Monday and Wednesday now have the same schedule). 6. Repeat steps as necessary for all the periods and days desired. Run Program 7. Press Run Program to return to normal operation. 45 Pub. No.
Clearing Schedule Period Suppose you want to skip a schedule period or periods for a particular day because you don’t need them. For example, if Saturday is a day you normally stay at home from school or work, you can clear the Leave and Return periods for this day and keep the Wake and Sleep periods. You can always reprogram the periods later. NOTE: The clear feature applies to 7-Day and 24-Hour Operation. The thermostat must be in the program mode to use the clear feature.
Day 2. For 7-Day Operation, press Day until the desired day displays. For 24-Hour Operation, skip to step 3. Setting Set Program System Heat AM Fan Sat On Heat Leave M14598 Press Day to select which day to begin clearing periods. Example display shows Saturday is selected 3. Press and hold Leave, Return or Sleep until the start time and temperature setting are cleared (approximately 3 seconds). Leave Return Setting Set Program Sat Sleep Leave NOTE: Wake cannot be cleared.
You do not have to program a replacement time for the remaining periods, for example Wake and Sleep. If you cleared only the Leave and Return periods for Saturday (or any day), the thermostat remains in the Wake period for all of Saturday until the Sleep period. 4. Repeat steps as necessary for all the periods to be cleared. Run Program 5. Press Run Program to return to normal operation. 48 Pub. No.
24-Hour Program and Operation Setting Set Program 24-Hour Operation is the same as 7-Day Operation except the same program repeats itself each day. Monday through Sunday follows the same exact schedule (four periods and up to eight temperatures). AM Fan Mon Tue Wed Thu Fri Sat Sun Wake Heat Auto M14600 During 24-Hour Operation, all days of the week display in program mode. 24-Hour Preprogrammed Schedule If your thermostat is set for 24-Hour Operation, follow the steps below.
The preprogrammed schedule is as follows (same schedule for all days of the week): You may keep this schedule or organize your own. Table 4. 24-Hour Preprogrammed Schedule. WAKE Program Repeats Every 24 Hours TIME FAN H 70 LEAVE 6:00 AM AUTO C 78 TIME FAN H 62 8:00 AM AUTO C 85 RETURN TIME FAN H 70 SLEEP 5:00 PM AUTO C 78 TIME FAN H 62 10:00 PM AUTO C 75 Customizing Your Own 24-Hour Schedule Before starting the programming procedure, use Tables 5 and 6 to organize your schedule.
Instructions 1. Write in the time you want each schedule period to begin. 2. Write in the heating temperature (H) and cooling temperature (C) you want for each period. 3. Circle the fan operation you desire for each period. 4. Begin programming. Table 6. An Extra 24-Hour Schedule.
1. Press Wake. Setting Set Program Wake AM Fan Mon Tue Wed Thu Fri Sat Sun Wake Heat Auto M14600 By pressing Wake, you enter the program mode. Example display shows 6:00 AM with Heat set to 70°F. 2. Press Time ▲ or Time ▼ until the desired Wake time displays. Time Setting Set Program AM NOTE: The program times are in fifteen minute intervals. (Example: 8:00, 8:15, 8:30). Fan Mon Tue Wed Thu Fri Sat Sun Wake Heat Auto M14601 By pressing Time, you select the time the Wake period will begin.
3. Press Increase ▲ or Decrease ▼ until the desired Wake temperature displays. NOTE: The setpoint temperature range is 55 to 85°F (13 to 29°C) for heating and 65 to 99°F (18 to 37°C) for cooling. Setting Set Program AM Fan Mon Tue Wed Thu Fri Sat Sun Wake Heat Auto M14602 By pressing Increase ▲ or Decrease ▼, you select the temperature for the Wake period. Example display shows the heating Wake period set for 68°. Fan NOTE: Press Fan to modify fan operation.
Heat/Cool Settings 4. Press Heat/Cool Settings to make selections for the opposite system setting (either Heat or Cool). Setting Set Program AM NOTE: If your system is set for Heat, only the heating temperature will be used. Similarly, if your system is set for Cool, only the cooling temperature will be used. If your system is set for Auto, either the heating or cooling temperature may be used depending on the temperature of the room.
5. Press Increase ▲or Decrease ▼ until the desired temperature setpoint displays. Setting Set Program AM Fan Mon Tue Wed Thu Fri Sat Sun Wake Cool Auto M14604 By pressing Increase ▲ or Decrease ▼, you select the cooling Wake temperature. Example display shows the cooling Wake period set for 76°. 6. Press Leave, Return or Sleep and repeat steps 2, 3, 4, and 5 for programming the rest of the day. The week is now programmed. Leave Run Program Return Sleep 7.
Constant Temperature Setpoint Programming Setting Set Program System Heat AM Unlike the first two options, Constant Temperature Setpoint Programming does not have the Wake, Leave, Return and Sleep periods. The temperature is set by pressing the ▲ and ▼ keys. Fan Mon Wake Heat Auto M14588 The four periods (for example, Wake) are absent from the display in this mode.
1. Press Increase ▲ or Decrease ▼ until the desired temperature displays. NOTE: The setpoint temperature range is 55 to 85°F (13 to 29°C) for heating and 65 to 99°F (18 to 37°C) for cooling. Setting Fan Heat Auto M14605 By pressing Increase ▲ or Decrease ▼, you select the heating temperature. Example display shows Heat is set for 68°. Fan NOTE: Press Fan to modify fan operation. Auto means the fan runs only when the heating or cooling equipment is operating.
3. Press Increase ▲ or Decrease ▼ until the desired temperature setpoint displays. Setting Cool M14606 By pressing Increase ▲ or Decrease ▼ after pressing , you select the cooling temperature. Example display shows Cool is set for 75°. NOTICE: This equipment is a Class B digital apparatus, which complies with Canadian Radio Interference Regulations, CRC c. 1374. CAUTION Equipment Damage Hazard. Can cause permanent damage to the compressor or other equipment.
TROUBLESHOOTING GUIDE Symptom Display does not come on. Possible Cause Thermostat is not being powered. Temperature setting The upper or lower temperature does not change limits were reached. (Example: cannot set the heating higher or the cooling lower). Action Check if the thermostat is mounted and latched on the wallplate—mount and latch the thermostat on the wallplate. Check if the circuit breaker is tripped—reset the circuit breaker. Check if the fuse is blown—replace the fuse.
Troubleshooting Guide (continued) Possible Cause Action Heating does not come on. Symptom No power to the thermostat. System selection is not set to Heat. Heating setpoint is below room temperature. Check that setpoint is above room temperature. Check if the circuit breaker is tripped—reset the circuit breaker. Check if the fuse is blown—replace the fuse. Check if the system switch at the equipment is in the Off position—set to On position. If 24 Vac is present, proceed with troubleshooting.
Troubleshooting Guide (continued) Symptom Possible Cause Action System on indicator (flame=heat, snowflake=cool) is lit, but no warm or cool air is coming from the registers. Heating/cooling equipment turns on Wait a minute after seeing the flame or snowflake and then check the fan when the equipment has the registers. reached the setpoint. System on indicator reads Filter and backlight is flashing. Filter expired. Refer to the Filter Indication section.
DEFINITIONS Adaptive Intelligent Recovery™ Control Adaptive Intelligent Recovery™ Control is the factory default setting that allows you to choose the exact time the room reaches your comfort temperature, as opposed to conventional recovery. Adaptive Intelligent Recovery™ Modes WAKE You choose the exact time the room reaches your comfort temperature after the SLEEP period.
If your thermostat is set to conventional recovery, a ❑ indication displays continuously, as shown on the example display. System Heat Recovery AM Fan Mon Sleep Room Heat Auto M14607 Conventional Recovery Modes WAKE You choose the time you want your heating or cooling system to start to reach your comfort temperature after the SLEEP period. Adjust this time to earlier when you know it will take longer for the system to reach your comfort temperature.
Preprogrammed Schedule The preprogrammed schedule consists of the four periods (Wake, Leave, Return and Sleep) and accompanying temperatures programmed into your thermostat at the factory. See Tables 1 and 4. Period One of the four times of the day (Wake, Leave, Return or Sleep) that you can program a setpoint or setpoints. Setpoint Setpoint is the temperature setting you select for a schedule or for a Hold. The setpoint can be either the heating temperature you set or the cooling temperature.
INDEX Filter Indication, 25 Information key, 23 keyboard, 7 LEAVE, 62, 63 options, 5 Outdoor Temperature, 23 Period, 64 Programming the First Day, 38 RETURN, 62, 63 Saturday, 19 Set Fan, 31 Set System, 31 Setpoint, 64 Setting Current Day and Time, 28 SLEEP, 62, 63 Thermostat Customer Assistance, 67 Troubleshooting, 59 Vacation, 19 WAKE, 62, 63 Warranty, 66 24-Hour Operation, 49 24-Hour Preprogrammed Schedule, 50 7-Day Operation, 32 7-Day Preprogrammed Schedule, 33 Adaptive Intelligent Recovery Control, 11
LIMITED WARRANTY Low Voltage Room Thermostats This warranty is extended by American Standard Inc., to the original purchaser and to any succeeding owner of the real property to which the Thermostat is originally affixed, and applies to products purchased and retained for use within the U.S.A. and Canada. If any part of your Thermostat fails because of a manufacturing defect within five years from the date of the original purchase, Warrantor will furnish without charge a new thermostat.
CUSTOMER ASSISTANCE If, after reading this guide, you have any questions concerning the operation of your thermostat, please call the Thermostat Customer Assistance Helpline at 1-800-500-2041. For service, contact your local heating and cooling contractor. 67 Pub. No.