<2. Handling Cautions>
2-4
IM 01C25B01-01E
IMPORTANT
For combined approval types
Once a device of multiple approval type is
installed, it should not be re-installed using any
other approval types. Apply a permanent mark
in the check box of the selected approval type
onthecerticationlabelonthetransmitterto
distinguish it from unused approval types.
IMPORTANT
All the blind plugs which accompany the EJX/
EJA-E transmitters upon shipment from the
factoryarecertiedbytheapplicableagencyin
combination with those transmitters. The plugs
whicharemarkedwiththesymbols“◊Ex”on
theirsurfacesarecertiedonlyincombination
with the EJX/EJA-E series transmitters.
2.9.1 FM Approval
a. FM Intrinsically Safe Type
Caution for FM intrinsically safe type. (Following
contents refer “DOC. No. IFM022-A12”)
Note 1. Model EJX/EJA-E Series Differential,
gauge and absolute pressure transmitters
with optional code /FS1 are applicable for
use in hazardous locations.
• ApplicableStandard:FM3600,FM3610,
FM3611, FM3810
• IntrinsicallySafeforClassI,Division1,
Groups A, B, C & D. Class II, Division 1,
Groups E, F & G and Class III, Division 1,
Class I, Zone 0 in Hazardous Locations, AEx
ia IIC
• NonincendiveforClassI,Division2,Groups
A, B, C & D. Class II, Division 2, Groups F &
G, Class I, Zone 2, Groups IIC, in Hazardous
Locations.
• Outdoorhazardouslocations,NEMATYPE
4X.
• TemperatureClass:T4
• Ambienttemperature:60to60°C
Note 2. Entity Parameters
• IntrinsicallySafeApparatusParameters
[Groups A, B, C, D, E, F and G]
Vmax = 30 V Ci = 6 nF
Imax = 200 mA Li = 0 µH
Pmax = 1 W
* Associated Apparatus Parameters
(FM approved barriers)
Voc≤30V Ca > 6 nF
Isc≤200mA La > 0 µH
Pmax≤1W
• IntrinsicallySafeApparatusParameters
[Groups C, D, E, F and G]
Vmax = 30 V Ci = 6 nF
Imax = 225 mA Li = 0 µH
Pmax = 1 W
* Associated Apparatus Parameters
(FM approved barriers)
Voc≤30V Ca > 6 nF
Isc≤225mA La > 0 µH
Pmax≤1W
• EntityInstallationRequirements
Vmax≥VocorUoorVt,Imax≥IscorIoorIt,
Pmax(orPo)≤Pi,CaorCo≥Ci+Ccable,
LaorLo≥Li+Lcable
Note 3. Installation
• Barriermustbeinstalledinanenclosurethat
meetstherequirementsofANSI/ISAS82.01.
• Controlequipmentconnectedtobarriermust
not use or generate more than 250 V rms or
V dc.
• Installationshouldbeinaccordancewith
ANSI/ISA RP12.6Installation of Intrinsically
SafeSystemsforHazardous(Classied)
Locations” and the National Electric Code
(ANSI/NFPA 70).
• Thecongurationofassociatedapparatus
must be FMRC Approved.
• Dust-tightconduitsealmustbeusedwhen
installed in a Class II, III, Group E, F and G
environments.
• Associatedapparatusmanufacturer’s
installation drawing must be followed when
installing this apparatus.
• Themaximumpowerdeliveredfromthe
barrier must not exceed 1 W.
• Noteawarninglabelworded
“SUBSTITUTION OF COMPONENTS MAY
IMPAIR INTRINSIC SAFETY,” and “INSTALL
IN ACCORDANCE WITH DOC. No. IFM022-
A12”