User`s manual

<2. Handling Cautions>
2-6
IM 01C25B01-01E
c. FM Intrinsically Safe Type/FM
Explosionproof Type
Model EJX/EJA-E Series pressure transmitters
with optional code /FU1 or /V1U1 can be
selected the type of protection (FM Intrinsically
Safe or FM Explosionproof) for use in
hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be in
accordance with the description about the
type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.
2.9.2 CSACertication
a. CSA Intrinsically Safe Type
Caution for CSA Intrinsically safe and
nonincendive type. (Following contents refer to
“DOC No. ICS013-A13”)
Note 1. Model EJX/EJA-E Series differential,
gauge, and absolute pressure transmitters
with optional code /CS1 are applicable for
use in hazardous locations
Certicate:1606623
[For CSA C22.2]
• Applicable Standard: C22.2 No.0, C22.2
No.0.4, C22.2 No.25, C22.2 No.94, C22.2
No.157, C22.2 No.213, C22.2 No.61010-1,
C22.2 No.60079-0
• Intrinsically Safe for Class I, Division 1,
Groups A, B, C & D, Class II, Division 1,
Groups E, F & G, Class III, Division 1
• Nonincendive for Class I, Division 2, Groups
A, B, C & D, Class II, Division 2, Groups F &
G, Class III, Division 1
• Enclosure: NEMA TYPE 4X
• Temp. Code: T4
• Amb. Temp.:–50* to 60°C
*–15°Cwhen/HEisspecied.
• Process Temperature: 120°C max.
[For CSA E60079]
• Applicable Standard: CAN/CSA E60079-11,
CAN/CSA E60079-15, IEC 60529:2001
• Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature: –50* to 60°C
*–15°Cwhen/HEisspecied.
• Max. Process Temp.: 120°C
• Enclosure: IP66/IP67
Note 2. Entity Parameters
• Intrinsicallysaferatingsareasfollows:
Maximum Input Voltage (Vmax/Ui) = 30 V
Maximum Input Current (Imax/Ii) = 200 mA
Maximum Input Power (Pmax/Pi) = 0.9 W
Maximum Internal Capacitance (Ci) = 10 nF
Maximum Internal Inductance (Li) = 0 µH
• Type"n"orNonincendiveratingsareas
follows:
Maximum Input Voltage (Vmax/Ui) = 30 V
Maximum Internal Capacitance (Ci) = 10 nF
Maximum Internal Inductance (Li) = 0 µH
• InstallationRequirements
Uo≤Ui,IoIi,Po≤Pi,
Co≥Ci+Ccable,Lo≥Li+Lcable
Voc≤Vmax,Isc≤Imax,
Ca≥Ci+Ccable,La≥Li+Lcable
Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
parameters of barrier.
Note 3. Installation
• Inanysafetybarreirusedoutputcurrent
must be limited by a resistor 'R' such that
Io=Uo/R or Isc=Voc/R.
• ThesafetybarriermustbeCSAcertied.
• Input voltage of the safety barrier must be
less than 250 Vrms/Vdc.
• Installation should be in accordance with
Canadian Electrical Code Part I and Local
Electrical Code.
• Dust-tight conduit seal must be used when
installed in Class II and III environments.
• Theinstrumentmodicationorparts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and Yokogawa Corporation
of America is prohibited and will void
Canadian Standards Intrinsically safe and
nonincendiveCertication.
F0204-1.ai
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
Pressure Transmitters
Safety Barrier
Supply
Hazardous Location Nonhazardous Location
General
Purpose
Equipment
+
+
+
+
[Intrinsically Safe]
Group IIC, Zone 0