User`s manual

<6. Wiring>
6-3
IM 01C25B01-01E
6.3.5 Status Output Connection
Whenoptioncode/ALisspecied,connectthe
external wiring as shown in Figure 6.5.
Tocongureandactivatetheprocessalarm
function and status output, it is necessary to set
some parameters. Refer to each communication
manual for procedures.
Transmitter
terminal box
Magnetic
valve
AC power supply
External power
supply 30V DC,
120mA max
+
250
24V DC
Use two-wire separately shielded cables.
Distributor
Shielded cable
F0605.ai
Figure 6.8 Status Output Connection
6.4 Wiring
6.4.1 LoopConguration
Since the DPharp uses a two-wire transmission
system for 4 to 20 mA output, signal wiring is also
used as power wiring.
DCpowerisrequiredforthetransmitterloop.The
transmitter and distributor are connected as shown
below.
For details of the power supply voltage and load
resistance, see section 6.6; for communications line
requirements,seesection9.1.
For 1 to 5 V output, three or four wire system is
used. See (3).
(1) 4 to 20 mA output, General-use Type and
Flameproof Type
Hazardous Location Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver
instrument
F0606.ai
Figure6.9 ConnectionbetweenTransmitterand
Distributor
(2) 4 to 20 mA output, Intrinsically Safe Type
With the intrinsically safe type, a safety barrier must
be included in the loop.
Hazardous Location Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver
instrument
Safety barrier
F0607.ai
Figure6.10 ConnectionbetweenTransmitterand
Distributor
(3) 1 to 5 V output
Either three or four wire system is used.
Power supply line and 1 to 5 V signal line commonly
use the SUPPLY - terminal.
NOTE
With three wire connection, the cable length may
affect the measurement accuracy of the output
signal.
In either three-wire or four-wire connection,
recommended wiring distance is 200 m or less,
and the use of shielded cable is recommended.
■ Threewireconnection
For three wire system, a negative wiring shall
be commonly used for power supply and signal
line.
Hazardous Location Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver
instrument
F0617.ai
Figure6.11 ConnectionbetweenTransmitter,
DistributerandReceiver