6.5 Grounding
Groundingisalwaysrequiredfortheproper
operation of transmitters. Follow the domestic
electricalrequirementsasregulatedineach
country. For a transmitter with a built-in lightning
protector, grounding should satisfy ground
resistanceof10Ωorless.
Ground terminals are located on the inside and
outside of the terminal box. Either of these terminals
may be used.
Ground terminal
(inside)
Ground terminal
(outside)
F0611.ai
Figure 6.16 Ground Terminals
6.6 Power Supply Voltage and
Load Resistance
For 4 to 20 mA output only.
Whenconguringtheloop,makesurethatthe
external load resistance is within the range in the
gurebelow.
(Note) In case of an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.
600
250
0 10.5 16.6 25.2 42
External
load
resistance
R (Ω)
Power supply voltage E (V DC)
F0612.ai
Communication
applicable range
BRAIN and HART
R=
E–10.5
0.0244
Figure6.17 RelationshipbetweenPowerSupply
Voltage and External Load Resistance