User`s manual

<7. Operation>
7-10
IM 01C25B01-01E
appropriate measure in reference to , “Errors and
Countermeasures” in each communication manual.
Note 3 : Changing the lower range value (LRV) also
automatically changes the upper range value (URV),
keeping the span constant. New URV=previous
URV+(new LRV–previous LRV)
7.6.11 Save or Cancel
At the end of each parameter setting, select “Save”
orCancel” by the external adjustment screw
and press the push button to save or cancel the
conguration.
Save? Saved
Save or Cancel
Cancel? Canceled
screw
F0716.ai
push
push
After
parameter
setting
7.6.12AbortConguration
7.6.12.1AbortConguration(Menu)
Hold down the push button for over 2 seconds to
exit the Local Parameter Setting mode.
Hold down the button
for over 2 seconds
Proccess Value
Process Measurement Display
Process Measurement Display
1. Tag Number
2. Press Unit
3. Press LRV
4. Press URV
5. Damping Time
6. Output Mode
7. Display Out1
8. LRV-Apply Press
9. URV-Apply Press
F0717.ai
Jump to the normal mode
7.6.12.2AbortConguration(Parameter)
Toexitthecongurationwhileeditingthevalue,
hold down the button for over 2 seconds and select
“Save” or “Cancel”.
F0718.ai
Return to
parameter review window
Save or Cancel?
Push for
Over 2 seconds
Tag editing
(3
rd
Character)
7.6.13LocalParameterSettingLock
To disable parameter changes by the Local
Parameter Setting there are three different ways.
Lockedfeatures
Communication Parameter
Ext SW =disable
(EXT ZERO ADJ = disable)
• ExternalZero
Adjustment
• LocalParameterSetting
Communication Parameter
Write Protect = On
(WRT PROTECT = Yes)
• LocalParameterSetting
• AllCommunication
Parameters *
Hardware write protection
switch on CPU assembly =
D (Disable)
• LocalParameterSetting
• AllCommunication
Parameters *
*External Zero Adjustment is unlocked.
The above parameter setting is carried out by
usingeldcommunicatororDTM.Seetheusers
manual IM 01C25T (HART/BRAIN) for the setting
procedure.
Reviewing local parameter setting by push button
on the integral indicator is available at any time
even when the Local Parameter Setting is locked.
7.6.14 Others
• DifferencebetweenBRAINandHART
HART BRAIN
Tag Number
Up to 8
characters can
be set
Up to 16
characters can
be set
Output Mode
(Linear/Sqroot)
“TRNS.FC
shown on the
integral indicator
“OUT.MOD
shown on the
integral indicator
• Thedegreeofadjustmentdependsonthe
speed of turning the adjustment screw. Turn the
screwslowlyfornetuningandturnthescrew
fastforquicktuning.