User`s manual

<9.GeneralSpecications>
9-19
IM 01C25B01-01E
9.3 OptionalSpecications
Item Description Code
Factory Mutual (FM) FM Explosionproof *
1
Explosionproof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
Hazardous(classied)locations,indoorsandoutdoors(NEMA4X)
FF1
FM Intrinsically safe *
1
*
3
Intrinsically Safe for Class I, Division 1, Groups A, B, C and D, Class II,
Division 1,Groups E, F and G and Class III, Division 1 Hazardous Locations.
Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II,
Division 2, Groups F and G, Hazardous Locations.
FS1
Combined FF1 and FS1 *
1
*
3
FU1
ATEX ATEX Flameproof *
1
II 2G, 2D Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db
Special fastener: ClassA2-50(A4-50) or more
KF22
ATEX Intrinsically safe Ex ia *
1
*
3
II 1G, 2D Ex ia IIC T4 Ga, Ex ia IIIC T85°C T100°C T120°C Db
KS21
Combined KF22, KS21 and ATEX Intrinsically safe Ex ic
*1*3
Ex ic: II 3G Ex ic IIC T4 Gc
KU22
Canadian Standards
Association (CSA)
CSA Explosionproof *
1
Explosionproof for Class I, Groups B, C and D
Dustignitionproof for Class II/III, Groups E, F and G
Enclosure TYPE 4X, Temp.Code:T6...T4
Ex d IIC T6...T4 Enclosure IP66/IP67
ProcessSealingCertication
DualSealCertiedbyCSAtotherequirementofANSI/ISA12.27.01
Noadditionalsealingrequired
Primary seal failure annuniciation: at the zero adjustment screw
CF1
CSA Intrinsically safe *
1
*
3
[For CSA C22.2]
Intrinsically safe for Class I, Division 1, Groups A, B, C and D, Class II,
Division 1, Groups E, F and G, Class III, Division 1
Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II,
Division 2, Groups F and G, Class III, Division 1
[For CSA E60079]
Ex ia IIC T4, Ex nL IIC T4
ProcessSealingCertication
DualSealCertiedbyCSAtotherequirementofANSI/ISA12.27.01
Noadditionalsealingrequired
Primary seal failure annuniciation: at the zero adjustment screw
CS1
Combined CF1 and CS1 *
1
*
3
CU1
IECEx IECExameproof*
1
Flameproof for Zone1, Ex d IIC T6...T4 Gb
Special fastener: ClassA2-50(A4-50) or more
SF2
IECExIntrinsicallysafe,typenandameproof*
1
*
3
Intrinsically safe and type n
Ex ia IIC T4, Ex nL IIC T4
Flameproof
Flameproof for Zone1, Ex d IIC T6...T4 Gb
Special fastener: ClassA2-50(A4-50) or more
SU2
Combination of Approval Combination of KU22, FU1 and CU1 V1U1
Painting Color change Terminal cover only
P
Bothsidesofampliercovers,Munsell7.5R4/14 PR
Coating change Anti-corrosion coating X2
316 SST exterior parts 316 SST name plate, tag plate and zero adjustment screw HC
Fluoro-rubber O-ring AllO-ringsofamplierhousing.Lowerlimitofambienttemperature:–1C(F) HE
Lightning protector Transmitter power supply voltage:
10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe type.)
Allowablecurrent:Max.6000A(1×40μs),Repeating1000A(1×40μs) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
A
Status output *
11
Transistor output (sink type)
Contact rating: 10.5 to 30 VDC, 120 mA DC(max) Low level: 0 to 2 VDC
AL