This water heater is a condensing type unit and requires a drain to be located in close
proximity to allow the condensate to drain safely. The condensate drains from the unit at the
base of the exhaust tee piece located near the bottom of the unit. The exhaust tee is
provided with a 32mm dia connection. A condense siphon is supplied in the flue kit which
should be connected to the 32mm connection at the base of the exhaust tee. The siphon
outlet must be connected to a 40mm dia OD plastic waste system. If the condense is allowed
to build-up then the exhaust outlet will become blocked and cause improper operation of the
water heater. The water heater will need to be raised off the floor on a concrete slab or base
or utilise or a low profile condensate pump to allow free drainage of condensate from the
outlet fitting. The condensate plastic drain pipe installation should slope to a suitable drain.
All models are equipped with a cleanout opening to aid the removal of hard water deposits
from the tank bottom. If this water heater operates under hard water conditions, the following
should be performed at least every 3 months: Turn off water supply and drain the water
heater. Remove the cleanout jacket cover and tank cover. When cleaning the tank, care
must be taken to avoid trying to break deposits loose as this could damage the glass lining
and shorten the life of the water heater. After cleaning, re-install the cleanout tank cover and
jacket cover, and refill with water. Refer to the section, “Section 6 Maintenance” in this
Installation and Operating Instruction manual for the procedures for filling and draining the
water heater.
All models are supplied complete with the Andrews Correx UP powered anode system. The
anodes are non-sacrificial and therefore do not require any maintenance or replacement. For
this reason the service clearance required above the water heater can be reduced quite
significantly. Correx anodes require a permanent power supply, this is all pre-wired and the
anode system can be located at the top of the heater beneath the top cover.
INSTALLATION SECTION 3
CONDENSATE
DRAIN
CLEANOUT
ELECTRICALLY
POWERED
ANODES
The service panel is located behind the service panel access cover, which is located by the
exhaust outlet tee piece near the bottom of the water heater. This panel contains a pressure
switch to monitor for excess pressure in the exhaust pipe from a blocked vent condition.
A collector high limit switch is used to monitor the ambient temperature between the first pass
collector and the exhaust collector. This is a manually re-settable switch. If this switch
continues to trip, please contact Andrews Water Heaters.
Access for servicing the water heater from the top is easy. Remove the two latches and the
metal screw at the front centre of the top to remove the lid for accessing the heater controls.
The lid must be replaced and re-latched upon completion for servicing.
SERVICE PANEL
ACCESS LID