Installation guide

INSTALLATION SECTION 3
T mmecnatsiDmuminiMhtiwsnoitisoPlanimre
A Directly below an opening, air brick, opening window etc. 300
B Above an opening, air brick, opening window etc. 300
C Horizontally to an opening, air brick, opening window etc. 300
D Below a gutter or sanitary pipework 75
E Below the eaves 200
F Below a balcony or carport roof 200
G Above ground, roof or balcony level 300
H F 051krowepiplios/niardlacitrevmor
J F 003renroclanretxerolanretninamor
K From a surface or boundary facing the terminal 600
L V 0051llawemasehtnolanimretamorfyllacitre
M Horizontally from a terminal on the same wall (up to 70kW) 300
(above 70kW) 600
N F 0021lanimretehtgnicaflanimretamor
P From a opening in a carport (e.g. door, windows) into the building 1200
Q Above roof 500
R F 005fooranoerutcurtslacitrevamor
S Above flat roof 1000
FLUE SYSTEMS
Likely flue positions requiring
a flue terminal guard
F
G
M
Q
R
L
G
F
P
B
C
R
K,N
A
A
H
J
J
D E
S
G
Q
S
25
Fig.3