Installation guide

TECHNICAL DETAILSSECTION 2
Model Reference - Natural Gas EC230/600 EC230/700 EC230/960 EC380/740 EC380/980 EC380/1220 EC380/1400
Model Reference - Propane LEC230/600 LEC230/700 LEC230/960 LEC380/740 LEC380/980 LEC380/1220 LEC380/1400
Natural gas, category I
2H
Gas consumption G20 3.41m
3
/h 4.09m
3
/h 5.43m
3
/h 4.09m
3
/h 5.43m
3
/h 6.82m
3
/h 7.92m
3
/h
Heat input gross 36.6 kW 43.9 kW 58.3 kW 43.9 kW 58.3 kW 73.2 kW 85.0 kW
Heat output 35.1 kW 41.3 kW 54.2 kW 43.0 kW 57.1 kW 71.0 kW 79.1 kW
Supply pressure 20 mbar 20 mbar 20 mbar 20 mbar 20 mbar 20 mbar 20 mbar
Gross thermal efficiency (NG) 96% 94% 93% 98% 98% 97% 93%
Propane, category I
3P
Gas consumption G31 1.39m
3
/h 1.67m
3
/h 2.22m
3
/h 1.67m
3
/h 2.22m
3
/h 2.78m
3
/h 3.12m
3
/h
Heat input gross 36.6 kW 43.9 kW 58.3 kW 43.9 kW 58.3 kW 73.2 kW 85.0 kW
Heat output 35.1 kW 41.3 kW 54.2 kW 43.0 kW 57.1 kW 71.0 kW 79.1 kW
Supply pressure 37 mbar 37 mbar 37 mbar 37 mbar 37 mbar 37 mbar 37 mbar
Gross thermal efficiency (propane) 96% 94% 93% 98% 98% 97% 96%
Noise level (a) 51dBA 51dBA 51dBA 51dBA 51dBA 51dBA 51dBA
Recovery rate thru’ 50ºC 600 ltrs/hour 700 ltrs/hour 960 ltrs/hour 740 ltrs/hour 980 ltrs/hour 1220 ltrs/hour 1400 ltrs/hour
Storage recovery time @50ºC rise 23mins 20mins 14mins 31mins 23mins 19mins 16mins
Concentric flue size (b) 100/150mm 100/150mm 100/150mm 100/150mm 100/150mm 100/150mm 100/150mm
Maximum flue run (concentric) 16 metres 16 metres 16 metres 16 metres 16 metres 16 metres 16 metres
Cold Inlet water connection 1
1
2"BSP 1
1
2"BSP 1
1
2"BSP 1
1
2"BSP 1
1
2"BSP 1
1
2"BSP 1
1
2"BSP
Hot outlet water connection 1
1
2"BSP 1
1
2"BSP 1
1
2"BSP 1
1
2"BSP 1
1
2"BSP 1
1
2"BSP 1
1
2"BSP
Drain port connection
3
4"BSP
3
4"BSP
3
4"BSP
3
4"BSP
3
4"BSP
3
4"BSP
3
4"BSP
Secondary return connection
3
4"BSP
3
4"BSP
3
4"BSP
3
4"BSP
3
4"BSP
3
4"BSP
3
4"BSP
Operating pressure (unvented) 3.5 bar 3.5 bar 3.5 bar 3.5 bar 3.5 bar 3.5 bar 3.5 bar
Maximum working pressure (vented) 10.3 bar 10.3 bar 10.3 bar 10.3 bar 10.3 bar 10.3 bar 10.3 bar
Maximum test pressure 20.7 bar 20.7 bar 20.7 bar 20.7 bar 20.7 bar 20.7 bar 20.7 bar
Gas connection (gas cock supplied)
3
4"BSP
3
4"BSP
3
4"BSP
3
4"BSP
3
4"BSP
3
4"BSP
3
4"BSP
Electrical supply 230V/50Hz 230V/50Hz 230V/50Hz 230V/50Hz 230V/50Hz 230V/50Hz 230V/50Hz
Power consumption 120W 120W 210W 120W 210W 210W 210W
Fuse 5amp 5amp 5amp 5amp 5amp 5amp 5amp
Weight empty 225kg 225kg 225kg 385kg 385kg 385kg 385kg
Weight full 450kg 450kg 450kg 760kg 760kg 760kg 760kg
Shipping weight 242kg 242kg 242kg 408kg 408kg 408kg 408kg
Shipping dimension - depth 889mm 889mm 889mm 889mm 889mm 889mm 889mm
Shipping dimension - width 819mm 819mm 819mm 819mm 819mm 819mm 819mm
Shipping dimension - height 1664mm 1664mm 1664mm 2197mm 2197mm 2197mm 2197mm
(a) Noise level measured at 2m from flue terminal.
(b) Reduce flue length by 1.2m for 90˚ bend, 0.7m for 45˚ bend and 1.5m for condense trap.
4