Installaon
Installaon Manual
For multiple sidewall exhaust terminations, an exhaust
termination must be at least 1 ft. (305mm) away from
another exhaust termination. An exhaust termination
must also be at least 2 ft. (610 mm) away from an inside
corner. (If the adjacent wall is less than 2 ft. (610 mm) of
length, the minimum required distance away from the
inside corner will be equal to the length of that adjacent
wall.)
Exhaust
termination
Inside
corner
1 ft.
(305 mm) min.
2 ft.
(610 mm) min.
1 ft. (305 mm)
min.
For multiple, direct-vent sidewall terminations that
combine the intake and exhaust into a single penetration,
space each direct-vent termination at least 1 ft. (305 mm)
away from each other, no matter the orientation. A direct-
vent termination must also be at least 2 ft. (610 mm) away
from an inside corner. (If the adjacent wall is less than 2 ft.
(610 mm) of length, the minimum required distance away
from the inside corner will be equal to the length of that
adjacent wall.)
Combined
intake and
exhaust
termination
Inside
corner
1 ft.
(305 mm) min.
2 ft.
(610 mm) min.
1 ft. (305 mm)
min.
For direct-vent sidewall
terminations that use two
separate penetrations for
the intake and exhaust,
keep the termination
clearances shown in the
diagrams on the right.
Exhaust
Intake
1 .
(305 mm)
min.
Exhaust
Intake
A
A
<Case2>
Exhaust
Intake
1. (305 mm)
min.
Exhaust
Intake
A
<Case1>
A
A:0.5ft.(159mm)
The clearance of A is recommended on the basis of the structure of the water heater.
*3inchand4inchventinstallationsonly