Spec Sheet

For more information, visit APC’s Web site at www.apc.com or call 800-800-4APC
17
For Business
Back-UPS Pro 280 Back-UPS Pro 420 Back-UPS Pro 650 Back-UPS Pro 1000 Back-UPS Pro 1400
PART NUMBER BP280S BP420S BP650S BP1000 BP1400
INPUT
Capacity 280VA (170W) 420VA (260W) 650VA (410W) 1000VA (670W) 1400VA (950W)
Nominal Input Vac single-phase, 50 or 60 Hz ± 5% (auto sensing)
OUTPUT
Voltage (on battery) Stepped approximation to sine wave output at 115 Vac ± 5% (auto sensing)
Automatic Voltage Regulation (AVR) Factory Default: (on line) Increases output up to 30% when input between 81Vac and 106Vac. User-selectable transfer point as low as 75Vac.
Decreases output up to 15% when input between 127Vac and 143Vac.User Selectable transfer point as high as 154Vac
SURGE PROTECTION
Dataline protection Single Line Phone/fax/modem/DSL/10-100 Base-T
PHYSICAL
Total number of receptacles 2 battery + surge, 1 surge only 3 battery + surge, 3 surge only 3 battery + surge, 3 surge only 6 battery + surge 6 battery + surge
Maximum Dimensions (H x W x L) 5.9” x 3.4” x 13.3” 6.6” x 4.7” x 14.5” 6.6” x 4.7” x 14.5” 8.5” x 6.7” x 17.3” 8.5” x 6.7” x 17.3”
(15.0 x 8.6 x 33.8 cm) (16.8 x 11.9 x 36.8 cm) (16.8 x 11.9 x 36.8 cm) (21.6 x 17.0 x 43.9 cm) (21.6 x 17.0 x 43.9 cm)
Net weight 16.6 lbs (7.9 kg) 21.6 lb (9.8 kg) 26.0 lb (11.8 kg) 42.6 lbs (19.3 kg) 54.1 lb (24.6 kg)
USER REPLACEABLE BATTERIES
Type User-replaceable, hot swappable, sealed, maintenance-free lead acid
Typical recharge time 2-4 hours 3-6 hours
DIAGNOSTICS AND MANAGEMENT
Visible indicators UPS On-line, on battery, UPS overload, replace battery, site wiring fault
Audible alarms On battery, low battery, UPS overload, replace battery
Management 14 Day automatic self-test, manual self-test
Serial DB9 RS-232 Connector PowerChute software with network manageability, data saving, unattended shutdown and UPS Optional network auto-shutdown software
diagnostics for Windows XP, Windows Me, Windows 98, Windows 95, Windows 2000 and Windows NT
CONFORMANCE
Agency approvals CSA, FCC Part15 Class B, FCC Part 68, UL 1778 CSA, FCC B, UL1778
Warranty 2 year comprehensive, including battery
Equipment Protection Policy $150,000 lifetime protection, including lightning (see policy for details)
TYPICAL RUNTIME IN MINUTES (Runtimes may vary depending on your equipment. For the most recent sizing information go to sizing.apcc.com)
Back-UPS Pro 280 Back-UPS Pro 420 Back-UPS Pro 650 Back-UPS Pro 1000 Back-UPS Pro 1400
Typical runtimes 14 20 45 79 145