Specifications

InRow Air Cooled RD Installation12
Connections Overview
All connections to and from the equipment can be made through either the top or the bottom of the
equipment. Once the corresponding connectors are sweated or brazed into place, the equipment can be
disconnected without soldering, welding, or gluing. See the following tables for information about the
sizes and types of connectors.
Warning: Make electrical connections in accordance with all local and national codes.
Power connections
Piping connections
Model Voltage
Frequency
(Hz) MCA MOP FLA
LRA
(Compressor)
ACRD100
208-240 60 25 40 N/A 87.5
ACRD101
220-240 50 N/A N/A 28 N/A
Above data is based on maximum operating conditions.
Consult local and national codes for wire size, conduit requirements and overload protection.
MCA - Minimum Circuit Ampacity
MOP - Maximum Overcurrent Protection
FLA - Full Load Amps
LRA - Locked Rotor Amps
Connection Type ACRD100/101
Refrigerant discharge
1-in Rotalock* 1/2-in OD
Refrigerant liquid
1-in Rotalock* 1/2-in OD
Condensate drain
3/16-in ID
5/16-in OD
* Use the provided Teflon
®
gasket to prevent leakage. Tighten the Rotalock nut to 75 Nm (55 lb-ft).