Specifications

InRow Air Cooled RD Installation22
Condensate pump
The condensate pumps
are factory-wired and piped
internally to the condensate pan. The pumps are capable
of moving liquid a maximum of 15.2 m (50.0 ft), which
may include a maximum lift of 4.9 m (16.0 ft) as
measured from floor level. For example, if your lift is
3 m (10 ft), you only have 12.2 m (40.0 ft) of usable run
remaining. The pumps also use on-board condensate
high level float switches, which are wired into the alarm
input for local and remote alarm capabilities.
Condensate pump drain connection. Sufficient
PVC drain line
is supplied to route the drain to the
outside of the equipment. Provide additional drain line at
installation to allow routing to a remote drain.
Warning: Do not exceed the lift or the run length of the drain system.
na2670a
Warning: To prevent equipment damage
from condensate, do not leave the conden-
sate drain line coiled inside the unit. Route
the condensate line out the top or bottom of
the unit as shown on the next page.