Quick Reference Smart-UPS® VT 10-40 kVA 380/400/415 V
Contents Model List............................................................................. 1 Features................................................................................ 2 Settings ................................................................................ 4 AC Input................................................................................ 5 AC Output............................................................................. 6 Efficiency........................................
Smart-UPS VT Fuses and Breakers ............................................................ 24 Fuse and Breaker Sizes .................................................................................... 26 Minimum Breaker Settings ............................................................................... 27 Communication and Management ..................................... 28 EPO ....................................................................................... 30 Compliance ...................
Model List UPS for up to 2 Battery Modules • Smart—UPS VT 10 kVA 400 V • Smart—UPS VT 15 kVA 400 V • Smart—UPS VT 15 kVA 400 V 3:1 • Smart—UPS VT 20 kVA 400 V • Smart—UPS VT 20 kVA 400 V 3:1 UPS for up to 4 Battery Modules • Smart—UPS VT 10 kVA 400 V • Smart—UPS VT 15 kVA 400 V • Smart—UPS VT 15 kVA 400 V 3:1 • Smart—UPS VT 20 kVA 400 V • Smart—UPS VT 20 kVA 400 V 3:1 • Smart—UPS VT 30 kVA 400 V • Smart—UPS VT 30 kVA 400 V 3:1 • Smart—UPS VT 40 kVA 400 V • Smart—UPS VT 40 kVA 400
Features Availability • Dual mains input: Increases availability by allowing the UPS to be connected to two separate power sources • Scalable runtime: Allows additional runtime to be quickly added as needed • Hot-swappable batteries: Ensure clean, uninterrupted power to protected equipment while batteries are being replaced • Generator compatible: Ensure clean, uninterrupted power to protected equipment when generator power is used • Automatic internal static bypass: Supplies utility power to the c
Protection • Frequency and voltage regulation: Gives higher application availability by correcting poor frequency and voltage conditions without using the battery • Safety-agency approved: Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.
Settings Default Settings System Settings (only updated when in load disconnect) Default setting Nominal output voltage (ph-ph) 380/400/415 V Frequency 50 Hz Frequency self-detect mode Auto Frequency range ±10 Hz Frequency slew rate 1 Hz/s Generator charge percentage 100% Cyclic charge mode enabled Off Auto start On Parallel UPS number 1 No.
AC Input Specifications 10 kVA 15 kVA Voltage 380 Connection type Hard Wire 5-wire (3PH + N + PE) 400 Input frequency (Hz) 40–70 I thd < 5% at full load Nom input current (A) 13.0 12.3 415 11.9 380 19.4 20 kVA 30 kVA 40 kVA 400 415 380 400 415 380 400 415 380 400 415 18.5 17.8 26.0 24.7 23.8 38.6 36.7 35.3 51.7 49.1 47.3 Max input current (A) 14.3 13.5 13.1 21.4 20.3 19.6 28.6 27.2 26.2 42.5 40.3 38.9 56.8 54.0 52.1 Input current limitation (A) 16.
AC Output Specifications 10 kVA 15 kVA 400 415 380 20 kVA Voltage (V) 380 Connection type Hard Wire 5-wire (3PH + N + PE) 400 Output capacity 150% for 1 minute (normal operation) 30 kVA 40 kVA 415 380 400 415 380 400 415 380 400 415 20.9 30.4 28.9 27.8 45.6 43.3 41.7 60.8 57.7 55.
Efficiency System 25% load 50% load 75% load 100% load 10 kVA 400 V 91.9 94.4 94.7 94.5 15 kVA 400 V 93.2 95.4 95.7 95.7 20 kVA 400 94.4 95.7 95.7 95.6 30 kVA 400 V 94 95.6 95.8 95.8 40 kVA 400 V 94.9 95.8 95.8 95.6 Efficiency Curves Low line is 348 V and high line is 452 V (+/- 13%).
15 kVA 400 V 20 kVA 400 V 8 Smart—UPS VT 10–40 kVA 380/400/415 V Quick Reference
30 kVA 400 V 40 kVA 400 V Smart—UPS VT 10–40 kVA 380/400/415 V Quick Reference 9
Derating due to Load Power Factor 10 Smart—UPS VT 10–40 kVA 380/400/415 V Quick Reference
Environmental Operating Temperature 0 - 40 °C Storage Temperature with batteries -15 - 45 °C Storage Temperature without batteries -30 - 70 °C Operating Relative Humidity 0 - 95%, non-condensing Storage Relative Humidity 0 - 95%, non-condensing Operating Elevation 0-1000 m: 100% load 1000–1500 m: 95% load 1500–2000 m: 91% load 2000–2500 m: 86% load 2500–3000 m: 82% load Storage Elevation 0-15000 meters Audible noise at 70% load – 1 meter from surface of unit 42.
Batteries Specifications Type VRLA Nominal voltage (VDC) +/- 192 Float voltage (VDC) +/- 219 End of discharge voltage (VDC) +/- 154 Battery current (at full load) 87.9 A at +/– 192 V Max. current (at end of discharge) 110.1 A at + 154 V Max. charging power 10 kVA: 800 15 kVA: 1200 20 kVA: 1600 30 kVA: 2400 40 kVA: 3200 Typical re-charge time 5 hours End voltage 1.6-1.
10 kVA 400 V Typical Performances Load kVA # of bat shelves 1 2 4 6 8 10 1 118 56 24 14 9 6 2 276 133 60 36 25 18 3 452 219 99 61 43 32 4 639 311 142 88 62 47 5 837 407 187 116 82 62 6 1043 508 233 145 103 78 7 1255 611 281 175 124 95 8 1474 718 331 206 147 112 9 1698 828 382 238 170 130 10 1928 940 433 271 193 148 11 2162 1054 486 304 217 166 12 2400 1171 540 338 241 185 13 2642 1289 595 372 266 204 14 2888
15 kVA 400 V Typical Performances Load kVA # of bat shelves 1 3 6 9 12 15 1 n.a. n.a. n.a. n.a. n.a. n.a.
20 kVA 400 V Typical Performances Load kVA # of bat shelves 2 4 8 12 16 20 1 n.a. n.a. n.a. n.a. n.a. n.a.
30 kVA 400 V Typical Performances Load kVA # of bat shelves 2 6 12 18 24 30 1 n.a. n.a. n.a. n.a. n.a. n.a. 2 n.a. n.a. n.a. n.a. n.a. n.a.
27 2765 863 390 242 171 131 28 2888 901 407 253 179 137 40 kVA 400 V Typical Performances Load kVA # of bat shelves 4 8 16 24 32 40 1 n.a. n.a. n.a. n.a. n.a. n.a. 2 n.a. n.a. n.a. n.a. n.a. n.a. 3 n.a. n.a. n.a. n.a. n.a. n.a.
24 1171 540 241 148 105 79 25 1230 568 253 156 110 84 26 1289 595 266 164 115 88 27 1349 623 278 171 121 92 28 1409 651 291 179 127 96 Battery Run-Times — Non-Modular Batteries • The below battery run-times are based on high quality batteries from approved manufacturers • The run-times are based on high rate batteries designed for UPS systems • The run-times are intended as a guide only, and APC disclaim the responsibility for these runtimes 10 kVA 400 V Battery Ah
24 22 49 37 29 24 20 17 14 30 28 65 49 39 32 27 23 20 38 35 88 67 53 44 37 31 27 50 47 123 94 75 62 52 45 39 65 60 170 130 104 86 73 63 55 30 kVA 400 V Battery Ah Load % 20 hr rate Approx.
End of Discharge Voltage 20 Smart—UPS VT 10–40 kVA 380/400/415 V Quick Reference
AC Bypass Specifications 10 kVA 380 V 15 kVA 400 V 415 V 380 V Connection type Hard Wire 5-wire (3PH + N + PE) Input frequency (Hz) 40–70 Nom input current (A) 15.2 14.4 13.9 22.8 20 kVA 30 kVA 40 kVA 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 21.7 20.9 30.4 28.9 27.8 45.6 43.3 41.7 60.8 57.7 55.
Physical Weights and dimensions Weight Height Width Depth w/o conduit box (with conduit box SUVTP10KH1B2S 245 1499 356 838 (925) SUVTP10KH2B2S 336 1499 356 838 (925) SUVTP10KH1B4S 382 1499 523 838 (925) SUVTP10KH2B4S 474 1499 523 838 (925) SUVTP10KH3B4S 566 1499 523 838 (925) SUVTP10KH4B4S 657 1499 523 838 (925) SUVTP15KH2B2S 433 1499 356 838 (925) SUVTP15KH2B4S 474 1499 523 838 (925) SUVTP15KH3B4S 566 1499 523 838 (925) SUVTP15KH4B4S 657 1499 523 838 (92
Cables Recommended Cable Sizes Note: Refer to IEC 60364-5-52 for installation methods. The recommended cable sizes are for installation method B2 and based on an environment with an ambient temperature of 30° C. Note: Temperature ratings of conductors: 70°C. Use only copper conductors and PVC isolated cables. 380 V, 400 V, and 415 V 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA Utility/mains input (mm2) 2.5 6 10 16 25 Static bypass input (mm2) 2.5 6 10 16 25 DC input (mm2) 50 50 50 50 50 2.
Fuses and Breakers Single Utility/Mains System • Q1: Utility/mains input • Q2: UPS output • Q3: Manual bypass • MBS: Mechanical bypass switch 24 Smart—UPS VT 10–40 kVA 380/400/415 V Quick Reference
Dual Utility/Mains Systen • Q1: Utility/mains input • Q2: UPS output • Q3: Manual bypass • Q5: Static bypass input • MBS: Mechanical bypass switch Smart—UPS VT 10–40 kVA 380/400/415 V Quick Reference 25
Parallel System • Q1: Utility/mains input • Q2: UPS output • Q3: Manual bypass • Q4: System output • Q5: Static bypass input Fuse and Breaker Sizes Single System 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA Mains input Q1 (A)1 16 25 35 50 63 Static bypass input Q5 (A) 16 25 35 50 63 UPS output Q2 (A) 16 25 35 50 63 1 Required upstream current protection: gL type fuse 26 Smart—UPS VT 10–40 kVA 380/400/415 V Quick Reference
Q3 and Q4 in Parallel Capacity Systems Units in parallel 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA 2 (A) 35 50 63 100 125 3 (A) 50 80 100 160 200 4 (A) 63 100 200 200 250 Q3 and Q4 in Parallel Redundant Systems (n+1) Units in parallel 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA 2 (A) 16 25 35 50 63 3 (A) 35 50 63 100 125 4 (A) 50 80 100 160 200 150% overload normal/battery operation 125% overload normal/battery operation Continuously Minimum Breaker Settings 800% overload
Communication and Management Network Management Card The system is equipped with one network management card for remote monitoring and control of an individual UPS by connecting it directly to the network. Input and Output Contacts Pins 7 and 8 are for external charge control. When 7 and 8 are closed, the UPS charges batteries with a pre-defined percentage (0-25-50-75-100%) of the maximum charging power. To be used in generator applications, or if special codes require control of charging.
Pin Description 8 External charging control return 7 External control of charging 6 Q3 active return 5 Q3 active 4 Battery measurement supply1 3 Battery unit quantity 1 2 Maximum battery temperature 1 1 Battery measurement return 1 1 To be used with APC XR Battery Enclosure.
EPO J108 Pin Connections Pin Description 1 Normally open EPO 2 Normally open EPO return 3 Normally closed EPO 4 Normally closed EPO return 5 + 24 V SELV supply 6 SELV ground EPO Options Dry Contacts Normally Open EPO is activated when pin 1 is connected to pins 3 and 5. Connections: 2-4-6, 3-5 and 1 (normally open) +24 V Normally Open EPO is activated when an isolated SELV 24 VDC voltage is supplied on pin 1 with reference to pin 2. Connections: 3-5 and 4-6.
Compliance Directives for CE marking 89/336/EDC Safety EN/IEC62040-1-1 73/237/EEC UL1778 EMC EN50091-2/IEC62040-2 FCC15A Performance Electromagnetic compatibility (EMC) EN/IEC62040-3 EN/IEC 61000-4-2 level 3, performance criteria A EN/IEC 61000-4-3 level 2, performance criteria A EN/IEC 61000-4-4 level 2, performance criteria A EN/IEC 61000-4-5 level 3, performance criteria A Smart—UPS VT 10–40 kVA 380/400/415 V Quick Reference 31
Options Parallel MBP — Wall-Mount • For a line-up-and-match solution with up to three UPS units in parallel • Two versions for 10-20 kVA and 30-40 kVA UPS units • Two ratings: 60 kVA and 120 kVA • Top or bottom cable entry • Including three communication boards • With lamps for status indication Empty Cabinet for batteries - floor-mount • For a line-up-and-match solution for 3rd party batteries • Up to eight trays for 32 customer-supplied batteries (16 on + bus and 16 and - bus).
Parallel Capabilities Up to four UPS units can be connected in parallel via the Parallel Communication Kit.
APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. – www.apc.com (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. – www.apc.com/support/ Global support searching APC Knowledge Base and using e-support.