Cut Sheet

Class I, Division 1 and 2 Groups A, B, C, D
Class II, Division 1 and 2 Groups E, F, G
Class III
Applications
UNY and UNF unions are used for joining conduit and
connecting conduit to enclosures. Facilitates modi cations,
permits removal of enclosures without turning or removal of
conduit.
Expansion unions compensate for expansion and contraction
of conduit.
Features
• Explosionproof, dust-ignitionproof.
Smooth, rounded integral bushing in each hub protects
conductor insulation.
Accurately tapped, tapered threads for tight, rigid joints and
ground continuity.
• Non-expansion unions
— Concentric ring interlocked design of 1/2”, 3/4” and 1” sizes
makes possible smaller diameter, allowing use in tighter
spaces. 1-1/4” and larger UNY sizes have removable male
nipple.
• Expansion unions
— One-piece design eliminates need for disassembly during
installation.
— Telescoping cylinder within cylinder design permits
expansion or contraction.
— Standard or long types available.
— Small external diameters—excellent in restricted areas in
wiring of pumps, motors, and other equipment.
— Internal phosphor bronze “bonding jumper” ring assures
positive ground between telescoping cylinders.
Standard Materials
UNY and UNF (non-expansion) unions:
— 1/2” thru 1”: steel or aluminum
— 1-1/4” thru 6”: malleable iron or copperfree (4/10 of 1%
max.) aluminum
UNY and UNF expansion unions: steel
UNL unions: malleable iron and steel
Standard Finishes
Malleable iron products: triplecoat — (1) zinc electroplate, (2)
chromate and (3) epoxy powder coat
Steel products: zinc electroplate
Aluminum products 1/2" thru 4": natural
Certifications and Compliances
UL Standard: 886 (1203)
UL Listed: E10444
CSA Standard: C22.2 No. 25, C22.2 No. 30
• CSA Certi ed: 065181
Options
PVC coating available on select unions. Add suf x -PVC to
catalog number.
Stainless steel UNF/UNY available 1/2", 3/4", and 1". Replace
suf xes NR or NR-A with SS.
Fittings
FITTINGS: HAZARDOUS CONDUIT FITTINGS
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© November 2011
162
UNY, UNF, and UNL Unions
Explosionproof, Dust-Ignitionproof
UNILETS
®
for Use with Threaded Rigid Metal Conduit and IMC.