Specifications

ASS
124
CN1
(optional)
(optional)
1
2
1
2
Indoor
unit
(sub)
(main)
Receiver unit
Remote controller
terminal board
Ground
Wireless remote
controller kit
Wired remote
controller
Remote control wiring (field supply)
When 1 indoor unit is operated with 2 remote controllers:
(The indoor unit runs according to which of the remote controllers is assigned as the main or sub unit.)
*
*
* Use field wiring cables with a
cross-sectional area of at least
0.5mm
2
to 2mm
2
.
* The maximum total length of
crossover cables must be no
longer than 400m.
CN1
(optional)
12
1
2
(optional)
Indoor
unit No.1
Indoor
unit No.2
Indoor
unit No.3
Indoor
unit No.4
Receiver
unit
(Main)
(Sub)
Remote controller
terminal board
When several groups of indoor units are operated with 2 remote controllers:
(The remote controller (main or sub unit) can operate with any indoor unit.)
Wireless remote
controller kit
Wired remote
controller
Remote control
wiring among the
control groups
(field supply)
* Use field wiring cables with a
cross-sectional area of at least
0.5mm
2
to 2mm
2
.
* The maximum total length of
crossover cables must be no
longer than 200m.
**
Ground
Ground Ground
Ground
Fig. 11-6
Fig. 11-5
(1) To assign the wired remote controller as the sub
unit, locate the address connector at the rear of
the wired remote controller PCB and disconnect it.
Reconnect it to the sub unit position.
(2) To assign the wireless remote controller as the
sub unit, locate the dip switch [S003] on the wire-
less receiver unit PCB. Set the No. 3 switch to the
ON position.
11-5. How to use the Test Run Setting
1. Set DIP switch [S003] No. 1 on the wireless
receiver unit PCB from OFF to ON.
2. All indicator lamps in the display section blink dur-
ing test run operation.
3. No temperature control is available during the test
run.
4. After the test run, be sure to reset DIP switch No.
1 back to the OFF position and check that no indi-
cator lamps are blinking. Then remount and attach
the PCB cover as before.
To avoid placing excessive operating load on the
equipment, use this function only when conducting
the test run.
NOTE
Receiver PCB
Receiver unit
cover
ON
1
2
3
4
Adjustable
corner cap
S003
Bit 1: OFF ON