11-18. How to Use the Test Run Setting
1. Set DIP switch [DS] No. 1 on the wireless receiver
unit PCB from OFF to the ON position.
2. All indicator lamps in the display section blink dur-
ing test run operation.
3. No temperature control is available during the test
run.
4. After the test run, be sure to reset DIP switch No.
1 back to the OFF position and check that no indi-
cator lamps are blinking.
Be aware that test run is not possible if the ceiling
panel is not attached.
To avoid placing an excessive load on the equip-
ment, use this function only when conducting the
test run.
NOTE
1234
OFF
DS switch “1”
Test run
Test
Sub remote
controller unit
Main remote
controller unit
ON
Normal
Fig. 11-21