Specifications

15
Table 1-17 Refrigerant Charge Amount at Shipment (for outdoor unit)
DC
AES06MI2H AES08MI2H AES10MI2H AES12MI2H
(kg)
7.5 10.0 10.0 10.0
AD
AES08M2H AES10M2H AES12M2H
(kg)
10.0 10.0 10.0
1-8. Combination of Outdoor Units
As shown in Table 1-18, a DC unit can be used independently or in combination with an AD unit.
1-9. System Limitations
Table 1-19 System Limitations
CAUTION
Sub units cannot be used independently.
Table 1-18 Combination of Outdoor Units
Total cooling capacity 16.0 22.4 28.0 33.5 40.0 45.0 50.4 56.0 61.5 68.0 73.0 78.5 85.0 90.0
(kW)
DC INV. unit (main) 06 08 10 12 06 08 10 10 12 12 10 10 10 12
AD unit (sub)
08 08 08 10 10 12 08 10 10 10
08 08 10 10
Total cooling capacity 96.0 101.0 106.5 113.0 118.0 123.5 130.0 135.0
(kW)
DC INV. unit (main) 12 12 10 10 12 12 12 12
12 12 10 10 10 12 12 12
AD unit (sub)
10 12 10 10 10 10 12 12
08 10 10 10 10 12
Max. No. allowable connected outdoor units 4
Max. capacity allowable connected outdoor units 135 kW (48 hp)
Max. connectable indoor units 40
Max. allowable indoor/outdoor capacity ratio 50 130 %