Specifications

27
Fig. 2-6
Fig. 2-7
Fig. 2-8
2-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc.
damp, humid or uneven locations
indoors (no-ventilation location)
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/
exhaust and possible maintenance.
Installation Space
Install the outdoor unit where there is enough space
for ventilation. Otherwise the unit may not operate
properly. Fig. 2-7 shows the minimum space require-
ment around the outdoor units when 3 sides are open
and only 1 side is shuttered, with open space above
the unit. The mounting base should be concrete or a
similar material that allows for adequate drainage.
Make provisions for anchor bolts, platform height, and
other site-specific installation requirements.
CAUTION
Leave space open above
the unit.
Construct louvers or other
openings in the wall, if
necessary, to ensure ade-
quate ventilation.
NOTE
Do not do any wiring or tubing within 30 cm of the
front panel, because it is needed as a servicing space
for the compressor.
2 in 1 row
2 in 2 rows
2 in 3 rows
3 in 1 row 4 in 1 row
4 in 2 rows
4 in 3 rows
3 in 2 rows
3 in 3 rows
Min.
0.6 m
Min.
0.6 m
Min.
0.6 m
Min.
0.9 m
Min.
0.9 m
Min.
1.0 m
Min.
1.0 m
Min.
1.0 m
Min.
1.0 m
Min.
1.3 m
Min.
1.3 m
Min.
1.3 m
Min.
1.3 m
Min.
1.3 m
Min.
1.3 m
Min.
1.3 m
Min.
1.3 m
Min.
0.9 m
Min.
0.9 m
Min.
0.9 m
Min.
0.9 m
Min.
0.9 m
Min.
1.1 m
Min.
1.1 m
Min.
1.1 m
Min.
1.4 m
Min.
1.4 m
Min.
1.6 m
Min.
1.6 m
Min.
1.6 m
Min.
1.6 m
Min.
1.4 m
Min.
1.4 m
Min.
1.1 m
Min.
0.9 m
Min.
0.6 m
0.6 m0.6 m0.6 m
0.6 m 0.6 m
0.6 m 0.6 m
0.6 m
0.6 m
Out-
door
unit
Heat
source
Hot air
Exhaust fan
More than 60 cm
More than
50 cm
More than
50 cm
More than 50 cm
Example of installation of 2 units
Conditions for installation: Fence height 1.8 m; effective opening ratio 50%; no raising for installation.
The distance between the units will vary with changes in installation conditions.
Multiple Installation Example
925925925
Installation anchor hole pitch
(3928)
830
925
909090
04-396 Inverter-W_a-p50 ARGO 12/21/04 9:38 AM Page 27