Specifications

AS2S
46
3-12. Checking the Drainage
After wiring and drain piping are completed, use the
following procedure to check that the water will drain
smoothly. For this, prepare a bucket and wiping cloth
to catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Remove the tube cover and through the opening,
slowly pour about 1,200 cc of water into the drain
pan to check the drainage.
(3) Short the check pin (CHK) on the indoor control
board and operate the drain pump. Check the
water flow through the transparent drain port and
see if there is any leakage.
(4) When the check of drainage is complete, open the
check pin (CHK) and remount the tube cover.
(Fig. 3-47)
CAUTION
CAUTION
Be careful since the fan will
start when you short the
pin on the indoor control
board.
To mount the tube cover,
use 4 × 8 tapping screws.
(Fig. 3-47)
Do not use long screws as
they may puncture the
drain pan and cause water
leakage.
Water for checking drainage
(Approx. 1,200 cc)
Drainage check section
(transparent drain port)
Inspection cover
Fig. 3-47