Specifications

ACS
55
Ceiling Mounted Type (ACS Type)
3-25. Required Minimum Space for Installation and Service
(1) Dimensions of suspension bolt pitch and unit
36, 56
73
106, 140
855
1125
1540
910
1180
1595
210
210
210
ABC
Length
Type
B
C
A
170
320
680
27.5
27.5
Ceiling side
(Suspension bolt pitch)
(Suspension bolt pitch)
Air intake
Air
(2) Refrigerant tubing • drain hose position
(3) Unit opening position (Refrigerant tubing • drain hose • power inlet port • remote controller wiring inlet port)
251 84 146 161
75 97 216
39
39
171
105
171
251
Wide tubing
Narrow
tubing
Right side
Left side
Rear (Figure shows view from front)
Closed with rubber stopper at time of shipment.
Left drain position Right drain position
(Narrow tubing
Wide tubing)
53
70
123
110 76
216
50130
Left-side drain hose
outlet port
Right-side drain
hose outlet port
Top outlet port
Remote
controller wiring
inlet port
(φ30, knock-out)
Power inlet port
(φ40, knock-out)
Power inlet port
(φ40, knock-out)
Knock-out
Side panel
Position of plate
inside side panel
Side panel
Left-side drain
hose outlet port
Rear tubing hole
84
32
32
60
171
347
125 72
85106
90
262
Remote controller
wiring inlet port
(φ30, rubber grommet
on right side only)
Outside air intake duct connection port
(φ100, knock-out)
Rear outlet port
*3
*1
*1
*2
*3
Fig. 3-80
Fig. 3-82
Fig. 3-81
*1 Use a compass saw, jig saw or simi-
lar tool and cut along the indented
portion of the side panel.
*2 If the optional drain up kit is installed,
this becomes the upper tubing outlet
port.
For details, refer to the manual for
the optional part.
*3 If the remote controller wiring inlet
port is changed to the left side or the
left top side, change the location of
the rubber grommet. Use aluminum
tape or similar material to seal the
unused inlet port on the right side.
Unit: mm
Unit: mm
Unit: mm
04-396 InverterW_p51-108 ARGO 12/21/04 10:17 AM Page 55