Specifications

ADPS
71
Air-outlet grille
Air-intake grille
Fig. 3-119
Fig. 3-120a
Fig. 3-120b
Fig. 3-120c
Min. 50 mm
Inspection plu
g
Min.
100 mm
Good
Min. 1/100
Not good
3-39. Installing the Drain Piping
(1) Prepare standard hard PVC pipe (O.D. 32 mm) for
the drain and use the supplied drain socket to pre-
vent water leaks. The PVC pipe must be pur-
chased separately.
When doing this, apply adhesive for the PVC pipe
at the connection point.
(2) If connecting a drain joint (supplied) to the thread-
ed drain port, first wrap the drain port threads with
sealing tape, then connect the joint. (Fig. 3-120a)
(3) After connecting the drain pipe securely, wrap
insulator (field supply) around the pipe.
(4) Ensure the drain pipe has a downward gradient
(1/100 or more) and prepare traps as indicated in
Fig. 3-120b.
(5) Also, in another part of the pipe arrangement, pre-
pare traps with an inspection plug to clean dust or
debris that may cause leaking of water. (Fig. 3-
120c)
(6) After connecting the drain piping, slowly pour
water into the drain pan to check that the water
drains smoothly.
Sealing tape
Drain joint
(supplied)
Drain pan
Drain opening
(25A male screw)
04-396 InverterW_p51-108 ARGO 12/21/04 10:17 AM Page 71