Specifications

ADPS
72
3-40. Caution for Ducting Work
This unit has high static pressure (applicable external
static pressure Max. 167 to 216 pa (1722 mm Aq).
In the case of small pressure resistance (for
instance, a short duct), install a damper for adjust-
ing air flow volume as air flow volume / air flow
noise increases.
If the air conditioner is to be installed in a room
such as an office or meeting room which needs a
low sound level, provide a supply and return noise
absorption chamber with an acoustic liner.
Include an air filter (field supply) at the return duct.
Indoor Fan Performance
How to Read the Diagram
The vertical axis is the External Static Pressure (mmAq) while the horizontal axis represents the Air Flow
(m
3
/minute). The characteristic curve for the H, Med, and Lo fan speed control.
The nameplate values are shown based on the H air flow. Therefore in the case of 73 Type, the flow is
23 m
3
/minute, while the External Static Pressure is 19 mmAq at H position. If the external static pressure is too
great (due to long extension of duct, for example), the air flow volume may drop too low at each air outlet.
External Static Pressure
Limit line
Limit line
H
H
M
M
L
Air Flow (m
3
/minute)
20
0
5
10
15
20
25
25 30
(Pa)
50
0
100
150
200
250
(mmAq)
Limit line
Limit line
H
H
M
M
L
25 30 35
Air Flow (m
3
/minute)
External Static Pressure
0
5
10
15
20
25
(Pa)
50
0
100
150
200
250
(mmAq)
Limit line
Limit line
H
H,M
M
L
30 35 40
Air Flow (m
3
/minute)
External Static Pressure
(Pa)
50
0
100
150
200
250
0
5
10
15
20
25
(mmAq)
NOTE
73 Type
106 Type 140 Type
H: At shipment
Fig. 3-121
04-396 InverterW_p51-108 ARGO 12/21/04 10:17 AM Page 72