Specifications

AFS
AFNS
78
Fig. 3-129
Fig. 3-130
Fig. 3-131
Fig. 3-132
Drain hose
Drain pipe (PVC)
Drain hose (supplied)
Drain insulator (supplied)
Vinyl clamp
(supplied)
Hose band
(supplied)
Hard PVC pipe
VP20
(field suppl
y
)
Insulating tape
(supplied)
Vinyl clamps
(supplied)
Drain hose insulator
(field supply)
Lead wire guide
Remote
controller
Screw
3-46. Installing the Drain Piping
(1) When rear-side drain piping is required bend the
drain hose attached to the indoor unit by 90°.
Connect a drain pipe (field supply) to the drain
hose through the rear tubing outlet in the rear
panel. Use a hard PVC pipe (VP20) for the drain
piping.
(2) Ensure that the drain pipe has a downward gradi-
ent of 1/100 or more and that there are no water
traps.
(3) Provide insulation for the drain pipe.
(4) After the drain piping is completed, pour water
into the drain pan to check if the water drains
smoothly.
(5) Remove any dust or debris in the drain pan so that
the pipe is not clogged.
3-47. Installing the Remote Controller
A remote controller (optional wired remote controller)
can be mounted in the indoor unit (floor-standing
type).
(1) Remove the cover of the optional wired remote
controller. (Fig. 3-131)
(2) Remove the front panel. Remove the screws and
fixture. (Fig. 3-132)
(3) Place the remote controller into the space in the
unit as shown in Fig 3-132. Assemble the lead
wires of the remote controller to its rear side cen-
ter and route them to the lead wire guide.
(4) Secure the fixture using the supplied screws.
CAUTION
Water leaks may occur
if the drain pipes are
connected inadequately.
To remove the cover from the remote controller, insert
a screwdriver between the cover and the controller as
shown in the figure above, and turn the screwdriver in
the direction indicated by the arrow.
04-396 InverterW_p51-108 ARGO 12/21/04 10:17 AM Page 78