4. HOW TO INSTALL THE OUTDOOR UNIT
4-1. Transporting
When transporting the unit, have it delivered as close
to the installation site as possible without unpacking.
Use a hook for suspending the unit. (Fig. 4-1)
When hoisting the unit, pass the lifting ropes under
the bottom plate as shown in the figure at right.
During hoisting, the angle between the ropes and
the top panel must be 70° or greater so that the
ropes do not touch (or damage) the fan guard.
(Use 2 ropes 7 meters in length or longer.)
In addition, when passing the ropes under the bot-
tom plate, adjust them so that the ropes are within
the supplied strips of cardboard on each side of the
bottom plate as shown in the figure.
Use panels or padding at each location where the
ropes contact the outer casing or other parts in
order to prevent these parts from being scratched
or damaged. In particular, use the supplied card-
board to prevent the top panel from being
scratched.
Be careful of the fan.
There is danger of injury if the fan starts to turn
during inspection. Be sure to turn OFF the remote
power switch before beginning inspection.
4-2. Installling the Outdoor Unit
(1) Use anchor bolts (M12) or similar to securely
anchor the unit in place. (Fig. 4-2)
(2) Be sure the rubber vibration insulator and platform
extend to the inside of the legs. In addition, the
washers used to anchor the unit from the top must
be larger than the installation anchor holes.
(Fig. 4-2 and 4-3)
Fig. 4-1
Supplied cardboard strips
Fan guard
Rope
70˚
Fig. 4-2
Fig. 4-3
20
A
B
44 64
The vibration insulator,
base, and platform must
accommodate all of the
bottom plate and insulation
anchor brackets (108 mm).
Outdoor unit
bottom plate
Installation anchor bracket
Vibration insulator
Anchor bolts (more than M12)
Washer
CAUTION
21.5
830
890
30
60
Installation anchor hole (15* 20)
(Detailed view of leg)
Fig. 4-4
A
830
B
890
Installation anchor hole (4 15* 20 hole)
(Anchor bolt positions)
Table 4-1
Type
08
06
08
10
12
10
12
783
A
B
823
925
965
965
925
Master unit (DC inverter unit)
Slave unit (constant speed unit)
Unit: mm
Unit: mm
Unit: mm
Unit: mm
04-396 InverterW_p51-108 ARGO 12/21/04 10:17 AM Page 79