NM Cable w/ Fill Units (or) Total Cables
Copper Conductors Per Cable of One Size
14/2 1 ea. 40
14/3 1.25 ea. 32
14/4 1.5 ea. 26
12/2 1.5 ea. 26
12/3 1.75 ea. 22
12/4 2 ea. 20
10/2 2 ea. 20
10/3 2.25 ea. 17
8/2 2.25 ea. 17
8/3 2.50 ea. 16
6/2 2.75 ea. 14
6/3 3 ea. 13
CABLEWAY
™
Cable Runway Support System
For Power OR Low Voltage Cable in New or Old Work
Arlington’s easy-to-install, non-metallic
C
ABLEWAY™ system is the answer to a
time-saving, UL Listed cable runway
support system.
New system components make it
even faster and easier to install.
• Support brackets attach directly to
framing members, without structural
damage. NEW styles include wall
mount and flat surface support
brackets.
They hold cables securely in place –
and you can open the bracket for
easier cable insertion and/or trough
installation!
• The slide-on five foot wire tray covers
and protects cable – install additional
trough sections as needed. They
join together with coupling.
• Angle and Tee make it easy to turn
corners.
• Push-on end caps complete the job!
For Power OR Low Voltage
Cable in New Construction
& Remodeling
MORE
on
Reverse
1 Stauffer Industrial Park
Scranton, PA 18517
800/233.4717
Fax 570/562.0646
www.aifittings.com
Arlington
Patents pending.
Example:
(19) 14/2 @ 1 = 19 Units
(8) 12/2 @ 1.5 = 12 Units
(4) 10/3 @ 2.25 = 9 Units
Total = 40 Units
Other Cable Combinations Not to Exceed 6 lbs./Linear Ft
Support
Bracket
T23H
End Cap
T23E
Coupling
T23C
5 ft
Trough
T205
Flat Surface
Support
Bracket
T23F
Wall Mount
Support
Bracket
T23W
Tee
T23T
Angle
T23A
Listed as a cable
runway support system