Humidifier User Manual

Drainage
Connect HC-6000 drain to suitable waste drainage
system. HC-6000 drain water may be as hot as 70°C
(158°F). Use clear drain hose provided and 25 mm (1”)
copper pipe pitched away from unit at 25 mm (1”)
inch per foot. An air gap to prevent back flow is required.
See Figure 7-1.
7
1-12 13-15 16-20 21-24 25-32 33-40 41-48 49-64 68-80 81-100 101-120 121-140 141-60
(AWG) 14 12 10 10 8 8 6 4 3 1 0 0 0
(mm2) 3 4 6 6 10 10 16 25 35 50 50 70 95
15 20 25 30 40 50 60 80 100 125 150 175 200
Table 7-1. Recommended Branch Circuits
Rating Amp
Wire
Circuit Breaker
Nominal
Amperage
Rating
Nominal
Amperage
Rating
Single Three Single Three
208 13.3 7.7 3.8 (8.3) 39 23 11 (24) 37 18 (40) 46 22 (48) 74 36 (80)
240 12.9 7.5 38 22 36 44 72
400 4.7 14 23 28 46
480 3.8 11 18 22 36
600 3 9 15 18 30
HC6100/HC6100DI
HC6300/HC6300DI
Table 7-2. Steam Capacities and Rating Amperages
Nominal
Amperage
Rating
Volts
(Vac)
Phase
3 KW Unit
15 KW Unit
Three
Phase
4.1 (9)
9 KW Unit
Nominal
Amperage Rating
Phase
12 (27)
Steam
Output
kg/hr
(lb/hr)
Steam
Output
kg/hr
(lb/hr)
20 (45)
25 (54)
41 (90)
Steam
Output
kg/hr
(lb/hr)
18 KW Unit
30 KW Unit
Three
Phase
Three
Phase
Steam
Output
kg/hr
(lb/hr)
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating Three
Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating Three
Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating Three
Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating Three
Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating Three
Phase
Steam
Output
kg/hr
(lb/hr)
208 84 41 (90) 125 61 (135)
240 96 54 (120)
400 51 45 (100) 73
480 58
600 47
65 (144)
Table 7-3. Steam Capacities and Rating Amperages
Volts (VAC)
HC6500/6500DI
30 KW Unit
33.5 KW Unit
40 KW Unit
48 KW Unit
45 KW Unit
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
240/220 144 82 (180) ————
400/380 77 30 (68) 110 145
480 87 116
600 70 93
98 (216)
130 (288)
Table 7-4. Steam Capacities and Rating Amperages
Volts
(Vac)
HC6500/HC6500DI
HC6700/HC6700DI
50.3 KW Unit
60 KW Unit
72 KW Unit
96 KW Unit
Air Gap
1” I.D. Clear Hose
Supplied with Unit
Fit Hose Inside
1-1/2” Pipe
1” or Larger
Copper Pipe
Figure 7-1 HC-6100/6300/6500/6700
Table 7-1. Recommended Branch Circuits
Table 7-2. Steam Capacities and Rating Amperages
Table 7-3. Steam Capacities and Rating Amperages
Table 7-4. Steam Capacities and Rating Amperages