6. INSTALLATION CHECKLIST BATTERY INSTALLATION
Battery is connected properly.
Recommended battery is installed.
Cables are clean and tight.
Terminals are coated with anti-corrosion grease, and
terminal covers are positioned.
FUEL SYSTEM
Complies with local and NFPA codes.
Fuel is connected and checked for leaks.
Correct fuel pressure (11-14 inches of water (0.6 psi) at
all load ranges).
Load block adjusted for maximum power for natural gas
fuel.
LOCATION
Unit is fastened to the appropriate mounting pad.
Louvers are free from obstruction.
Exhaust is clear of flammable objects and debris.
ELECTRICAL CONNECTIONS
Complies with local code requirements and all National
Electrical Codes.
Utility is connected and present.
Transfer switch is connected.
All wires running outside of the generator are in NEC-
approved conduit. *Note: Utility wires and transfer switch
control wires must be in separate conduit.
Unit is grounded to an approved earth ground.
COOLING AND VENTILATING
All inlets and outlets are free from obstruction.
OTHER
Verify that the unit is filled to the proper level with the
proper break-in oil. Adjust as required.