Operating instructions

AMC-DTR Sensor Transmitter User Manual
30
Chan 1 Manual Offset Real 41019 4 NA
Chan 1 Manual Offset Devisor 41020 4 NA
Chan 2 Cal Zero Real 41021 4 NA
Chan 2 Cal Zero Devisor 41022 4 NA
Chan 2 Cal Span Real 41023 4 NA
Chan 2 Cal Span Devisor 41024 4 NA
Chan 2 Zero Real 41025 4 NA
Chan 2 Zero Devisor 41026 4 NA
Chan 2 Span Real 41027 4 NA
Chan 2 Span Devisor 41028 4 NA
Chan 2 Fault Real 41029 4 NA
Chan 2 Fault Devisor 41030 4 NA
Chan 2 Alarm 1 Real 41031 4 NA
Chan 2 Alarm 1 Devisor 41032 4 NA
Chan 2 Alarm 2 Real 41033 4 NA
Chan 2 Alarm 2 Devisor 41034 4 NA
Chan 2 Alarm 3 Real 41035 4 NA
Chan 2 Alarm 3 Devisor 41036 4 NA
Chan 2 Manual Gain Real 41037 4 NA
Chan 2 Manual Gain Devisor 41038 4 NA
Chan 2 Manual Offset Real 41039 4 NA
Chan 2 Manual Offset Devisor 41040 4 NA
Binary Cal Data:
Chan 1 A2D MIN 41041 4 NA
Chan 1 A2D MAX 41042 4 NA
Chan 1 D2A MIN 41043 4 NA
Chan 1 D2A MAX 41044 4 NA
Chan 2 A2D MIN 41045 4 NA
Chan 2 A2D MAX 41046 4 NA
Chan 2 D2A MIN 41047 4 NA
Chan 2 D2A MAX 41048 4 NA
Min and Max calibration points for the A/D and D/A converters.
7.11 System Security
The SYSTEM SECURITY menu offers two levels of protection. A LOW level allows CAL MODE
sensor calibrations but requires the 4-digit Pass Code prior to altering menus. HIGH level locks
the entire menu database and the CAL Mode until the correct Pass Code is entered. LOW and
HIGH security levels always allow viewing of configuration menus but they may not be changed.
Contact Name is a 12 character ASCII field available for displaying a phone # or name of
personal who know the Pass Code. Lost Pass Codes may be recovered by entering the
locked security menu and holding the UP key for 5 seconds. The 4-digit code appears near the
bottom of the screen.
S Y S T E M S E C U R I T Y
C o n t a c t N a me
S e c u r e L e v e l L OW
P a s s C o d e
U n l o c k e d
Figure 29: System Security Menu