Product specifications

19
4.8 Condensate disposal
The appliance is provided with a 25 mm flexible pipe from its
condensate trap. As given in §Error! Reference source not found.,
this should be inserted into an open waste pipe of not less than 32 mm
diameter, together with the safety discharge pipe. The condensate is
slightly acidic (pH between 3 and 6) and should be disposed of in the
following ways, using suitable plastic waste pipe (Note: copper or steel
must not be used):-
internal stack pipe (see diagram)
waste pipe (see diagrams)
external drain or gulley
purpose made soak-away
The pipe work must incorporate a minimum fall of 2.5 degrees (or
44mm/metre) towards its point of termination. Condensate pipe work
external to the property, or in an unheated space (eg a garage), must be
protected against freezing through the use of pipe insulation and trace
heating. Atmos can supply trace heating.
If an external drain or gulley is used, then the open end of the pipe
should be terminated below the grid level, but above the water level.
If a proprietary soak-away is used, install at least 1 metre away from the
external wall and clear of foundations and services. The soak-away is
buried in the ground and surrounded by limestone chippings to
neutralise the condensate.