User manual

User Manual Page 12 of 74
(PVI-6000-OUTD-UK-W Rev.1.0)
B) The resulting DC output is connected to the AURORA input and converted
into AC power with the appropriate voltage and frequency to be exported to
the grid.
Fig. 2 - Wind Turbine – Generator
WARNING: The DC voltage input to the inverter shall not exceed 600Vdc
for any reason, in order to avoid damage to the equipment.
NOTE: A minimum input voltage of 50Vdc is required for the AURORA inverter to
start the grid connection sequence. Once connected, the AURORA inverter
will transfer the maximum power available for any input DC voltage value in
a 50V to 580Vdc range to the grid.
The max output current from the generator or an interface device shall be always
within the inverter limits. In the AURORA inverter the total max input current is
36Adc.
Wind Turbine
Generator