3.6 Electrical Connections
Step 1/6: Open the AC grid disconnect switch
Step 2/6: Open the Wind Generator AC disconnect breaker.
Step 3/6: Unscrew the 4 screws to open the front panel
Step 4/6: Connect the inverter to the AC grid disconnect switch
WARNING: Use suitable low-impedance cables to connect the inverter to
the AC disconnect switch.
WARNING: The inverter must be connected to the AC grid disconnect
switch using a three-wire cable with two line wires and a neutral wire.
1) Route the cable from the inverter to the AC disconnect
2) Connect the three-pole cable to AURORA using the cable gland on the
case
3) Connect the three wires as follows:
- terminal 1 – to Line
- terminal 2 – to Neutral
- Terminal 3 – no connection
- Screw terminal – Protection earth
Fig.11 - AC wire terminal block
NOTE: If you have installed a meter between the AC disconnect and the
AURORA inverter, follow the procedure outlined above when connecting to
the meter.