Step 5/6: Connect AURORA to the Rectifier/Wind Interface Box
WARNING: Prior to connecting the AURORA inverter to the rectifier
check, using a proper meter, that the polarity and the voltage value between
the positive and negative terminal are correct. The output voltage polarity
from the rectifier should match the “+” and “-” symbols.
Referring to Fig.12 use the following procedure:
1) Verify the presence of the two wires connecting the two DC input
channels in parallel (the inverter is shipped from the factory with the
two wires already connected).
2) Connect the positive DC cable from the rectifier or Wind Interface to the
positive terminal block inside the AURORA inverter (red cable on Fig
12).
3) Connect the negative DC cable from the rectifier or Wind Interface to
the negative terminal block inside the AURORA inverter (black cable
on Fig 12).