5.5.6.6 Time
This function allows time and date setting.
5.5.6.7 Language
It is possible to set the national language or English.
5.5.6.8 START UP voltage
Start-up voltage can be set according to the characteristics of the wind
turbine/generator system. Voltage range can be 50V to 350V. The default setting is
50V. This parameter can be changed by means of the display keys.
5.5.6.9 Autotest
Self-test to verify correct operation of the protection and the grid interface device, as
required by UL 1741 standard.
Press ENTER to access all information of this section:
OV = Max. voltage
UV = Min. voltage
OF = Max. Frequency
UF = Min. Frequency
DC injection = DC component of the output current. This component shall not exceed
>0.5% of the inverter maximum rated current or the unit will switch off.
OV test
UV test
OF test
UF test
DC in