Manual ON and OFF input is read on inverter digital input. When set to OFF, the
display will cycle through the following screens:
5.5.6.12 UV Prot.time
This function is used to set the inverter connection time after the input voltage drops
below the undervoltage protection threshold that is set at 40V.
For example: if UV Prot.time is set at 60 seconds, and Vin voltage drops below 40V at
9:00am the inverter will stays connected to the grid (at 0 power) until 9:01am.
Power-One sets this time at 60 seconds. The user can change this setting and set it
from 1 second to 3,600 seconds.
5.5.6.13 Alarm Message
Is possible to program the error message to be shown in the display using the
following procedure:
Press to access the following submenu:
Use the button on the left side of the display to move UP (switch 2) and DOWN
(switch 3) the arrow and press ENTER (switch 4) to select the desiderate function.
Once the menu ENABLE/DISABLE is selected the following screen will appear. It is
possible to enable or disable the custom error message function in this screen:
Select the line ENABLE MESSAGE and press ENTER, the following screen will
appear on the display:
Alarm message
Enable / Disable
Com
p
ose messa
g
e
Enable / Disable
Com
p
ose messa
g
e
Enable message
Disabile messa
g
e
Remote OFF
Waiting Rem.ON…
….to restart